- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Flame Retardance:
- V1 conforming to UL 94
- Protective Treatment:
- TH IEC 60068-2-30
- Mechanical Durability:
- 10 Mcycles
- Protective Cover:
- with
- Average Impedance:
- 1.5 mOhm - Ith 80 A 50 Hz for power circuit
- Country of Origin:
- France
- Coil Technology:
- built-in bidirectional peak limiting diode suppressor
- Device Short Name:
- LC2D
- Time Constant:
- 34 ms
- Ambient Air Temperature For Operation:
- -40-60°C || 60-70°C with derating
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
- Climatic Withstand:
- IACS E10 || IEC 60947-1 Annex Q category D
- Inrush Power In W:
- 19-19 W 20°C)
- Fire Resistance:
- 850°C IEC 60695-2-1
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Motor Power Kw:
- 15 kW at 220...230 V AC 50-60 Hz || 22 kW at 380...400 V AC 50-60 Hz || 30 kW at 500 V AC 50-60 Hz || 33 kW at 660...690 V AC 50-60 Hz || 25 kW at 415 V AC 50-60 Hz || 30 kW at 440 V AC 50-60 Hz
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Power Dissipation Per Pole:
- 3.7 W AC-3 || 9.6 W AC-1 || 3.7 W AC-3e
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Tightening Torque:
- control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connecto
- Rated Breaking Capacity:
- 900 A at 440 V for power circuit conforming to IEC 60947
- Warranty:
- 18 months
- Device Presentation:
- preassembled with reversing power busbar
- Overvoltage Category:
- III
- Pollution Degree:
- 3
- Reach Free Of Svhc:
- Yes
- Range:
- TeSys || TeSys Deca
- Control Circuit Type:
- DC standard
- Eu Rohs Directive:
- Compliant
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Product Certifications:
- UL || CSA || RINA || GOST || CCC || DNV || LROS (Lloyds register of shipping) || GL || BV || UKCA
- Electrical Durability:
- 1.45 Mcycles 50 A AC-3 <= 440 V || 0.5 Mcycles 80 A AC-1 <= 440 V || 1.45 Mcycles 50 A AC-3e <= 440 V
- Weight:
- 2.03 kg
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Control Circuit Voltage Limits:
- 0.1...0.3 Uc -40-70°C drop-out DC || 0.75...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
- [Icw] Rated Short-Time Withstand Current:
- 400 A 40°C - 10 s for power circuit || 810 A 40°C - 1 s for power circuit || 84 A 40°C - 10 min for power circuit || 208 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
- Interlocking Type:
- mechanical
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Mounting Support:
- plate || rail
- Contactor Application:
- motor control || resistive load
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Ambient Air Temperature For Storage:
- -60-80°C