- Inrush Power In Va:
- 140-140 VA 60 Hz cos phi 0.75 (at 20°C) || 160-160 VA 50 Hz cos phi 0.75 (at 20°C)
- Tightening Torque:
- control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connecto
- Mechanical Durability:
- 6 Mcycles
- Average Impedance:
- 1.5 mOhm - Ith 80 A 50 Hz for power circuit
- Sustainable Offer Status:
- Green Premium product
- Device Short Name:
- LC2D
- Interlocking Type:
- mechanical
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Range:
- TeSys || TeSys Deca
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 80 A (at 60°C) for power circuit
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 100 A gG at <= 690 V coordination type 1 for power circuit || 100 A gG at <= 690 V coordination type 2 for power circuit
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Control Circuit Type:
- AC 50/60 Hz
- Pollution Degree:
- 3
- Eu Rohs Directive:
- Compliant
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Rohs Exemption Information:
- Yes
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Electrical Durability:
- 1.45 Mcycles 50 A AC-3 <= 440 V || 1.1 Mcycles 80 A AC-1 <= 440 V || 1.45 Mcycles 50 A AC-3e <= 440 V
- [Ie] Rated Operational Current:
- 50 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 80 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 50 A (at <60°C) at <= 440 V AC AC-3e for power circuit
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Net Weight:
- 1.88 kg
- Mounting Support:
- rail || plate
- Country of Origin:
- France
- Mercury Free:
- Yes
- Fire Resistance:
- 850°C IEC 60695-2-1
- [Icw] Rated Short-Time Withstand Current:
- 400 A 40°C - 10 s for power circuit || 810 A 40°C - 1 s for power circuit || 84 A 40°C - 10 min for power circuit || 208 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
- Weight:
- 1.88 kg
- Control Circuit Voltage Limits:
- 0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
- Width:
- 119 mm
- Motor Power Kw:
- 15 kW at 220...230 V AC 50-60 Hz || 22 kW at 380...400 V AC 50-60 Hz || 30 kW at 500 V AC 50-60 Hz || 33 kW at 660...690 V AC 50-60 Hz || 25 kW at 415 V AC 50-60 Hz || 30 kW at 440 V AC 50-60 Hz
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
- Contactor Application:
- resistive load || motor control
- Hold-In Power Consumption In Va:
- 13-13 VA 60 Hz cos phi 0.3 (at 20°C) || 15-15 VA 50 Hz cos phi 0.3 (at 20°C)
- Product Name:
- TeSys D || TeSys Deca
- Environmental Disclosure:
- ENVPEP1503009EN
- Mechanical Robustness:
- vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
- Warranty:
- 18 months
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 900 A at 440 V for power circuit conforming to IEC 60947
- Coil Technology:
- without built-in suppressor module
- Connections - Terminals:
- control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit scr
- Rated Breaking Capacity:
- 900 A at 440 V for power circuit conforming to IEC 60947
- Poles Description:
- 3P
- Ambient Air Temperature For Storage:
- -60-80°C