- Halogen Content Performance:
- Halogen free plastic parts & cables product
- Pollution Degree:
- 3
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Net Weight:
- 2.174 kg
- Electrical Durability:
- 1.8 Mcycles 57 A AC-3 <= 440 V || 0.5 Mcycles 80 A AC-1 <= 440 V
- Product Or Component Type:
- reversing contactor
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- [Icw] Rated Short-Time Withstand Current:
- 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms for Signaling circuit || 520 A 40°C - 10 s for power circuit || 900 A 40°C - 1 s for power circuit || 110 A 40°C - 10 min for power circuit || 260 A 40°C - 1
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Mechanical Robustness:
- vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
- Overvoltage Category:
- III
- [Ie] Rated Operational Current:
- 80 A (at <60°C) at <= 440 V AC-1 for power circuit || 65 A (at <60°C) at <= 440 V AC-3 for power circuit
- Connections - Terminals:
- control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit scr
- Product Name:
- Tesys Deca green || TeSys Deca
- Device Presentation:
- preassembled with reversing power busbar
- Inrush Power In W:
- 11-11 W 20°C
- Poles Description:
- 3P
- Range:
- TeSys || TeSys Deca
- Heat Dissipation:
- 0.5-0.5 W
- Ambient Air Temperature For Operation:
- -40-60°C || 60-70°C with derating
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- [Ue] Rated Operational Voltage:
- power circuit 690 V AC 25...400 Hz
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Height:
- 122 mm
- Device Short Name:
- LC2D
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 1000 A at 440 V for power circuit conforming to IEC 60947
- Interlocking Type:
- mechanical
- Environmental Disclosure:
- ENVPEP1607010EN
- Flame Retardance:
- V1 conforming to UL 94
- Control Circuit Type:
- DC DC low consumption
- Average Impedance:
- 1.5 mOhm - Ith 80 A 50 Hz for power circuit
- Signaling Circuit Frequency:
- 25...400 Hz
- Sustainable Offer Status:
- Green Premium product
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Fire Resistance:
- 850°C IEC 60695-2-1
- Pole Contact Composition:
- 3 NO
- Rated Breaking Capacity:
- 1000 A at 440 V for power circuit conforming to IEC 60947
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Protective Treatment:
- TH IEC 60068-2-30
- [Uc] Control Circuit Voltage:
- 24 V DC
- Color:
- Gray SE GREY 6) || Green SE GREEN 2)
- Mercury Free:
- Yes
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Depth:
- 120 mm
- Hold-In Power Consumption In W:
- 0.5-0.5 W 20°C
- Eu Rohs Directive:
- Compliant with Exemptions
- Control Circuit Voltage Limits:
- <= 0.1 Uc -40-70°C drop-out DC || 0.8...1.2 Uc -40-60°C operational DC || 1...1.2 Uc 60-70°C operational DC
- Maximum Horse Power Rating:
- 5 hp at 115 V AC 60 Hz for 1 phase motors || 10 hp at 230/240 V AC 60 Hz for 1 phase motors || 20 hp at 200/208 V AC 60 Hz for 3 phase motors || 20 hp at 230/240 V AC 60 Hz for 3 phase motors || 40 hp at 460/480 V AC 60 Hz for 3 phase motors || 50 hp