- Ambient Air Temperature For Operation:
- -40-60°C || 60-70°C with derating
- Operating Time:
- 16...24 ms opening || 42.5...57.5 ms closing
- Mechanical Durability:
- 10 Mcycles
- Environmental Disclosure:
- ENVPEP1503009EN
- Device Presentation:
- preassembled with reversing power busbar
- Rated Breaking Capacity:
- 1000 A at 440 V for power circuit conforming to IEC 60947
- Pvc Free:
- Yes
- Mounting Support:
- rail || plate
- Fire Resistance:
- 850°C IEC 60695-2-1
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Eu Rohs Directive:
- Compliant
- Signaling Circuit Frequency:
- 25...400 Hz
- Coil Technology:
- built-in bidirectional peak limiting diode suppressor
- [Ie] Rated Operational Current:
- 80 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 65 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 65 A (at <60°C) at <= 440 V AC AC-3e for power circuit
- Interlocking Type:
- mechanical
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
- Mechanical Robustness:
- vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
- Pollution Degree:
- 3
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Connections - Terminals:
- control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit scr
- Range:
- TeSys || TeSys Deca
- [Icw] Rated Short-Time Withstand Current:
- 520 A 40°C - 10 s for power circuit || 900 A 40°C - 1 s for power circuit || 110 A 40°C - 10 min for power circuit || 260 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms
- Height:
- 122 mm
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Power Dissipation Per Pole:
- 9.6 W AC-1 || 6.3 W AC-3 || 6.3 W AC-3e
- Depth:
- 120 mm
- Control Circuit Voltage Limits:
- 0.1...0.3 Uc -40-70°C drop-out DC || 0.75...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
- Control Circuit Type:
- DC standard
- Electrical Durability:
- 1.45 Mcycles 65 A AC-3 <= 440 V || 1.4 Mcycles 80 A AC-1 <= 440 V || 1.45 Mcycles 65 A AC-3e <= 440 V
- Flame Retardance:
- V1 conforming to UL 94
- Weight:
- 2.04 kg
- Climatic Withstand:
- IACS E10 || IEC 60947-1 Annex Q category D
- Contactor Application:
- resistive load || motor control
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Circularity Profile:
- ENVEOLI1503009EN
- Device Short Name:
- LC2D
- Protective Treatment:
- TH IEC 60068-2-30
- Warranty:
- 18 months
- Protective Cover:
- with
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Product Or Component Type:
- reversing contactor
- Pole Contact Composition:
- 3 NO
- Country of Origin:
- France