LC2D65AEHE is a 3-pole TeSys D reversing contactor from Schneider Electric for motor applications. Rated 65A AC-3 30kW@400V, it includes a 48-130V AC/DC low consumption electronic coil, 2NO+2NC aux contacts, a mechanical interlock. LC2D65AEHE is a 3-pole TeSys D reversing contactor from Schneider Electric for motor applications up to 30kW@400V. It includes a 48-130V AC/DC low consumption electronic coil and 2NO+2NC built-in auxiliary contacts, NC mirror certified. Compact, DIN-rail mounting, with mechanical interlock and pre-wired reversing circuit, it procures reliability and durability. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Compact product, 119mm wide, for DIN-rail and panel mounting. Assembled with mechanical interlock and pre-wired reversing circuit. Clear separation between power and control circuits, easy front access to coil and auxiliary contacts connections. Equipped with an electronic coil, wide band voltage 48-130V, AC/DC compatible, low consumption. Provides 4 built-in auxiliary contacts 2NO + 2NC, NC contacts are mirror certified suitable to be included in the control of safety systems. High electrical durability, guaranteed for 1.6 million cycles at 65A AC-3 440V, for demanding motor switching applications. Robust design with high making and breaking capacities up to 20 In. Power connections by EverLink BTR screw terminals providing constant tightening pressure.
- Inrush Power In Va:
- 23-23 VA 50/60 Hz 20°C)
- Signaling Circuit Frequency:
- 25...400 Hz
- Device Short Name:
- LC2D
- Tightening Torque:
- control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connecto
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- [Icw] Rated Short-Time Withstand Current:
- 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms for Signaling circuit || 520 A 40°C - 10 s for power circuit || 900 A 40°C - 1 s for power circuit || 110 A 40°C - 10 min for power circuit || 260 A 40°C - 1
- Pollution Degree:
- 3
- Height:
- 122 mm
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Device Presentation:
- preassembled with reversing power busbar
- Contactor Application:
- motor control || resistive load
- Sustainable Offer Status:
- Green Premium product
- Utilisation Category:
- AC-1 || AC-3
- Operating Time:
- 55...65 ms closing || 20...120 ms opening >= 17221) || 20...80 ms opening >= 18011)
- Control Circuit Type:
- AC 50/60 Hz AC/DC electronic || DC AC/DC electronic
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Weight:
- 2.174 kg
- Power Dissipation Per Pole:
- 9.6 W AC-1 || 6.3 W AC-3
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 80 A (at 60°C) for power circuit
- Color:
- Gray SE GREY 6) || Green SE GREEN 2)
- Pole Contact Composition:
- 3 NO
- Net Weight:
- 2.174 kg
- Circularity Profile:
- ENVEOLI1607010EN
- Product Or Component Type:
- reversing contactor
- Standards:
- EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
- Rohs Exemption Information:
- Yes
- Product Certifications:
- CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping) || UKCA
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 1000 A at 440 V for power circuit conforming to IEC 60947
- Poles Description:
- 3P
- Coil Technology:
- built-in bidirectional peak limiting
- Protective Cover:
- with
- Ambient Air Temperature For Storage:
- -60-80°C
- Protective Treatment:
- TH IEC 60068-2-30
- [Ie] Rated Operational Current:
- 80 A (at <60°C) at <= 440 V AC-1 for power circuit || 65 A (at <60°C) at <= 440 V AC-3 for power circuit
- Interlocking Type:
- mechanical
- Mounting Support:
- rail || plate
- Connections - Terminals:
- control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit scr
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Heat Dissipation:
- 0.9-0.9 W 50/60 Hz
- Width:
- 119 mm
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
- Ambient Air Temperature For Operation:
- -40-60°C || 60-70°C with derating
- Motor Power Kw:
- 18.5 kW at 220...230 V AC 50 Hz || 30 kW at 380...400 V AC 50 Hz || 37 kW at 415 V AC 50 Hz || 37 kW at 440 V AC 50 Hz || 37 kW at 500 V AC 50 Hz || 37 kW at 660...690 V AC 50 Hz
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Average Impedance:
- 1.5 mOhm - Ith 80 A 50 Hz for power circuit
- Range:
- TeSys || TeSys Deca
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-1
- Overvoltage Category: