Schneider Electric

Schneider Electric LC2D80004M5 TeSys Deca changeover contactor , 4P(4 NO) , AC-1 , <= 440V, 125A, 220V AC coil

(No reviews yet) Write a Review
SKU:
LC2D80004M5
MPN:
LC2D80004M5
Condition:
New
Circularity Profile:
N/A
Climatic Withstand:
IACS E10
Warranty:
18 months
Control Circuit Type:
AC 50 Hz
Coil Technology:
without built-in suppressor module
Pvc Free:
Yes
Toxic Heavy Metal Free:
Yes
Eu Rohs Directive:
Compliant
Interlocking Type:
mechanical
Device Short Name:
LC2D
[Uc] Control Circuit Voltage:
220 V AC 50 Hz
Mechanical Robustness:
vibrations contactor open2 Gn, 5...300 Hz || shocks contactor open8 Gn for 11 ms || vibrations contactor closed3 Gn, 5...300 Hz || shocks contactor closed10 Gn for 11 ms
Rated Breaking Capacity:
1100 A at 440 V for power circuit conforming to IEC 60947
[Icw] Rated Short-Time Withstand Current:
135 A 40°C - 10 min for power circuit || 320 A 40°C - 1 min for power circuit || 640 A 40°C - 10 s for power circuit || 990 A 40°C - 1 s for power circuit
Depth:
158 mm
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-55°C drop-out AC 50 Hz || 0.85...1.1 Uc -40-55°C operational AC 50 Hz
Environmental Disclosure:
ENVPEP110205EN
Mercury Free:
Yes
Protective Treatment:
TH IEC 60068-2-30
Rohs Exemption Information:
Yes
Ip Degree Of Protection:
IP20 front face IEC 60529
Reach Free Of Svhc:
Yes
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Device Presentation:
preassembled, with prewired power connections
Power Dissipation Per Pole:
12.5 W AC-1
Protective Cover:
without
Sustainable Offer Status:
Green Premium product
Associated Fuse Rating:
200 A gG at <= 690 V coordination type 1 for power circuit || 160 A gG at <= 690 V coordination type 2 for power circuit
Pollution Degree:
3
Poles Description:
4P
Overvoltage Category:
III
Tightening Torque:
control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector flat Ø 6 to Ø 8 mm || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.
Heat Dissipation:
6-10 W 50 Hz
[Ie] Rated Operational Current:
125 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 80 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 80 A (at <60°C) at <= 440 V AC AC-3e for power circuit || 55 A (at <60°C) at <= 400 V AC AC-4 for power circuit
Average Impedance:
0.8 mOhm - Ith 125 A 50 Hz for power circuit
Product Or Component Type:
changeover contactor
Product Certifications:
UL || CSA || RINA || CCC || DNV-GL || LROS (Lloyds register of shipping) || BV || UKCA || EAC || CB
Operating Altitude:
0...9842.52 ft (0...3000 m)
Hold-In Power Consumption In Va:
20-20 VA 50 Hz cos phi 0.3 (at 20°C)
Irms Rated Making Capacity:
1100 A at 440 V for power circuit conforming to IEC 60947
Mechanical Durability:
10 Mcycles
Standards:
CSA C22.2 No 60947-4-1 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Pole Contact Composition:
4 NO
Flame Retardance:
V1 conforming to UL 94
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Inrush Power In Va:
200-200 VA 50 Hz cos phi 0.75 (at 20°C)
Width:
207 mm
$1,343.10