Schneider Electric

Schneider Electric LC2D80AKUE TeSys Deca reversing contactor 3P 66A AC-3/AC-3e up to 440V coil 100-250V AC/DC

(No reviews yet) Write a Review
SKU:
LC2D80AKUE
MPN:
LC2D80AKUE
Condition:
New
Halogen Content Performance:
Halogen free plastic parts & cables product
Fire Resistance:
850°C IEC 60695-2-1
Interlocking Type:
mechanical
[Ue] Rated Operational Voltage:
power circuit 690 V AC 25...400 Hz
Product Name:
Tesys Deca green || TeSys Deca
Auxiliary Contact Composition:
1 NO + 1 NC
Contactor Application:
resistive load || motor control
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Environmental Disclosure:
ENVPEP1607010EN
Control Circuit Voltage Limits:
<= 0.1 Uc -40-70°C drop-out AC/DC || 0.85...1.1 Uc -40-60°C operational AC/DC || 1...1.1 Uc 60-70°C operational AC/DC
Range:
TeSys || TeSys Deca
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 1000 A at 440 V for power circuit conforming to IEC 60947
[Icw] Rated Short-Time Withstand Current:
100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms for Signaling circuit || 520 A 40°C - 10 s for power circuit || 900 A 40°C - 1 s for power circuit || 110 A 40°C - 10 min for power circuit || 260 A 40°C - 1
Sustainable Offer Status:
Green Premium product
Signaling Circuit Frequency:
25...400 Hz
Flame Retardance:
V1 conforming to UL 94
Height:
122 mm
Weight:
2.174 kg
Insulation Resistance:
> 10 MOhm for Signaling circuit
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connecto
Ambient Air Temperature For Storage:
-60-80°C
Pollution Degree:
3
Climatic Withstand:
IACS E10 || IEC 60947-1 Annex Q category D
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Product Or Component Type:
reversing contactor
Device Presentation:
preassembled with reversing power busbar
Electrical Durability:
1 Mcycles 66 A AC-3 <= 440 V || 0.5 Mcycles 80 A AC-1 <= 440 V || 1 Mcycles 66 A AC-3e
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 80 A (at 60°C) for power circuit
Inrush Power In Va:
18-18 VA 50/60 Hz 20°C)
Pole Contact Composition:
3 NO
Utilisation Category:
AC-1 || AC-3 || AC-3e
Country of Origin:
United States
Net Weight:
2.174 kg
Protective Treatment:
TH IEC 60068-2-30
Mechanical Durability:
6 Mcycles
Depth:
120 mm
Mercury Free:
Yes
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Eu Rohs Directive:
Compliant with Exemptions
Heat Dissipation:
1.2-1.2 W 50/60 Hz
[Uc] Control Circuit Voltage:
100...250 V AC 50/60 Hz || 100...250 V DC
Rohs Exemption Information:
Yes
Product Certifications:
CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping) || UKCA
Coil Technology:
built-in bidirectional peak limiting
Power Dissipation Per Pole:
9.6 W AC-1 || 6.5 W AC-3 || 6.5 W AC-3e
$1,005.00

Description

TeSys D reversing contactor, 3 poles (3NO), for motor control applications up to 9A/690V AC-3 (4kW@400V). It provides low consumption 100-250V AC/DC coils with electronic control, 2NO+2NC built-in auxiliary contacts (NC mirror contacts), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (90mm width), DIN-rail mounting or screw fixing. With pre-wired reversing power connections, mechanical interlock (without electrical interlocking). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
View AllClose