Schneider Electric LC2DT25E7 TeSys Deca changeover contactor - 4P(4 NO) - AC-1 - <= 440 V 25 A - 48 V AC coil
Schneider Electric
$420.00
LC2DT25E7 is a Schneider Electric 4-pole (4NO) TeSys D changeover contactor for AC-1 load applications up to 25A/690V. It provides 48V 50/60Hz AC coils, 2NO+2NC built-in auxiliary contacts (NC mirror contacts), power and control connections by screw clamp terminals. Equipped with pre-wired changeover power connections, and mechanical interlock. Compact (90mm width), DIN-rail mounting, it procures high reliability and durability. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). With pre-wired changeover power connections, mechanical interlock (without electrical interlocking). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Toxic Heavy Metal Free:
- Yes
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Mercury Free:
- Yes
- Tightening Torque:
- power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || contro
- Operating Time:
- 12...22 ms closing || 4...19 ms opening
- Pvc Free:
- Yes
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 40 A gG at <= 690 V coordination type 1 for power circuit || 25 A gG at <= 690 V coordination type 2 for power circuit
- Protective Cover:
- with
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Irms Rated Making Capacity:
- 250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
- Device Presentation:
- preassembled, with prewired power connections
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Width:
- 90 mm
- Warranty:
- 18 months
- Product Name:
- TeSys D || TeSys Deca
- Rated Breaking Capacity:
- 250 A at 440 V for power circuit conforming to IEC 60947
- Net Weight:
- 0.73 kg
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Ambient Air Temperature For Storage:
- -60-80°C
- [Icw] Rated Short-Time Withstand Current:
- 30 A 40°C - 10 min for power circuit || 61 A 40°C - 1 min for power circuit || 105 A 40°C - 10 s for power circuit || 210 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
- Fire Resistance:
- 850°C IEC 60695-2-1
- Connections - Terminals:
- power circuit screw clamp terminals 1 1-4 mm²flexible without cable end || power circuit screw clamp terminals 2 1-4 mm²flexible without cable end || power circuit screw clamp terminals 1 1-4 mm²flexible with cable end || power circuit screw clamp
- Height:
- 85 mm
- Mechanical Durability:
- 15 Mcycles
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Climatic Withstand:
- IACS E10 || IEC 60947-1 Annex Q category D
- [Uc] Control Circuit Voltage:
- 48 V AC 50/60 Hz
- Signaling Circuit Frequency:
- 25...400 Hz
- Control Circuit Voltage Limits:
- 0.3...0.6 Uc -40-60°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz
- Contactor Application:
- resistive load
- Ambient Air Temperature For Operation:
- -40-60°C || 60-70°C with derating
- Product Or Component Type:
- changeover contactor
- Mounting Support:
- rail || plate
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Inrush Power In Va:
- 70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
- Mechanical Robustness:
- vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
- Electrical Durability:
- 0.8 Mcycles 25 A AC-1 <= 690 V
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Poles Description:
- 4P
- Pollution Degree:
- 3
- Utilisation Category:
- AC-1
- Circularity Profile:
- ENVEOLI1501004
- Eu Rohs Directive:
- Compliant
- Flame Retardance:
- V1 conforming to UL 94
- Rohs Exemption Information:
- Yes