[Ith] Conventional Free Air Thermal Current:
20 A (at 60°C) for power circuit || 10 A (at 50°C) for Signaling circuit
Control Circuit Voltage Limits:
operational: 0.8...1.15 Uc (at <50°C) || drop-out: 0.2...0.75 Uc (at <50°C)
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Product Or Component Type:
reversing contactor
Device Short Name:
LC2K
Eu Rohs Directive:
Compliant
Device Presentation:
preassembled with reversing power busbar
Signaling Circuit Frequency:
<= 400 Hz
Auxiliary Contact Composition:
1 NC
Minimum Switching Current:
5 mA for Signaling circuit
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Height:
58 mm
Non Overlap Distance:
0.5 mm
Tightening Torque:
0.8-1.3 N.m screw clamp terminals Philips No 2 || 0.8-1.3 N.m screw clamp terminals flat Ø 6 mm || 0.8-1.3 N.m screw clamp terminals pozidriv No 2
Pole Contact Composition:
3 NO
Mechanical Robustness:
shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on X axis6 Gn for 11
Operating Altitude:
6561.68 ft (2000 m) without derating
Associated Fuse Rating:
25 A gG at <= 440 V for power circuit || 25 A aM for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947 || 10 A gG for Signaling circuit conforming to VDE 0660
Flame Retardance:
V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
Heat Dissipation:
1.3-1.3 W
Inrush Power In Va:
30-30 VA (at 20°C)
Range:
TeSys
Mounting Support:
rail || plate
Overvoltage Category:
III
Rohs Exemption Information:
Yes
Sustainable Offer Status:
Green Premium product
Width:
90 mm
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Protective Treatment:
TC IEC 60068 || TC DIN 50016
Auxiliary Contacts Type:
instantaneous 1 NC
Ambient Air Temperature For Storage:
-50-80°C
Motor Power Kw:
1.5 kW 220...230 V AC 50/60 Hz || 2.2 kW 380...415 V AC 50/60 Hz || 3 kW 440/690 V AC 50/60 Hz
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Reach Free Of Svhc:
Yes
Poles Description:
3P
Maximum Operating Rate:
3600 cyc/h
Utilisation Category:
AC-3 || AC-3e || AC-4
Mechanical Durability:
5 Mcycles
Hold-In Power Consumption In Va:
4.5-4.5 VA (at 20°C)
Device Application:
control
[Ue] Rated Operational Voltage:
power circuit 690 V AC 50/60 Hz || Signaling circuit <= 690 V AC 50/60 Hz
Connections - Terminals:
screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 mm²flexible with cable end || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 2 0.75-4
Environmental Disclosure:
ENVPEP1503003EN
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Country of Origin:
United States
Insulation Resistance:
> 10 MOhm for Signaling circuit
Ambient Air Temperature For Operation:
-25-50°C
Electrical Durability:
1.3 Mcycles 6 A AC-3 <= 440 V || 1.3 Mcycles 6 A AC-3e <= 440 V || 0.05 Mcycles 36 A AC-4 <= 440 V
Rated Breaking Capacity:
110 A at 220...230 V conforming to IEC 60947 || 110 A at 380...400 V conforming to IEC 60947 || 110 A at 415 V conforming to IEC 60947 || 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conformin
$130.00

Description

LC2K0601U7 is a compact 3-pole TeSys K reversing contactor from Schneider Electric for motor applications. Rated 6A AC-3 2.2kW@400V, it includes a 240V 50/60Hz AC coil, 2NC auxiliary contacts, a mechanical interlock and pre-wired reversing circuit. LC2K0601U7 is a 3-pole TeSys K reversing contactor from Schneider Electric for simple motor applications rated up to 2.2kW@400V. Very compact, DIN-rail compatible, with connections by screw clamp terminals, it is assembled with a mechanical interlock and a pre-wired reversing circuit. It includes a 240V 50/60Hz AC coil and 2NC built-in auxiliary contacts. Available worldwide, it complies with multi-standards (IEC, UL, CSA, CCC, EAC, Marine) and is certified Green Premium (RoHs/Reach). Very compact, 90mm wide, for DIN-rail and panel mounting. Assembled with mechanical interlock and pre-wired reversing circuit. Provides a 240V AC coil compatible 50/60Hz and 2NC built-in auxiliary contact. Can be completed with auxiliary contact blocks (LA1K, LA2K) and thermal relays (LR2K).