- Net Weight:
- 0.39 kg
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Ip Degree Of Protection:
- IP20 VDE 0106
- Flame Retardance:
- V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
- Heat Dissipation:
- 1.3-1.3 W
- Product Or Component Type:
- reversing contactor
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Hold-In Power Consumption In Va:
- 4.5-4.5 VA (at 20°C)
- Device Application:
- control
- Rohs Exemption Information:
- Yes
- Reach Free Of Svhc:
- Yes
- Ambient Air Temperature For Storage:
- -50-80°C
- Inrush Power In Va:
- 30-30 VA (at 20°C)
- Device Presentation:
- preassembled with reversing power busbar
- [Uc] Control Circuit Voltage:
- 48 V AC 50/60 Hz
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Toxic Heavy Metal Free:
- Yes
- Product Certifications:
- CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
- Country of Origin:
- France
- Circularity Profile:
- ENVEOLI1503003EN
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Average Impedance:
- 3 mOhm - Ith 20 A 50 Hz for power circuit
- Associated Fuse Rating:
- 25 A gG at <= 440 V for power circuit || 25 A aM for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947 || 10 A gG for Signaling circuit conforming to VDE 0660
- Pole Contact Composition:
- 3 NO
- Control Circuit Voltage Limits:
- operational: 0.8...1.15 Uc (at <50°C) || drop-out: 0.2...0.75 Uc (at <50°C)
- Device Short Name:
- LC2K
- Non Overlap Distance:
- 0.5 mm
- [Icw] Rated Short-Time Withstand Current:
- 90 A 50°C - 1 s for power circuit || 85 A 50°C - 5 s for power circuit || 80 A 50°C - 10 s for power circuit || 60 A 50°C - 30 s for power circuit || 45 A 50°C - 1 min for power circuit || 40 A 50°C - 3 min for power circuit || 80 A - 1 s for Signali
- Warranty:
- 18 months
- [Ith] Conventional Free Air Thermal Current:
- 20 A (at 50°C) for power circuit || 10 A (at 50°C) for Signaling circuit
- Protective Treatment:
- TC IEC 60068 || TC DIN 50016
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV
- Utilisation Category:
- AC-4 || AC-1 || AC-3 || AC-3e
- [Ie] Rated Operational Current:
- 20 A (at <50°C) at <= 440 V AC AC-1 for power circuit || 16 A (at <70°C) at 690 V AC AC-1 for power circuit || 9 A at <= 440 V AC AC-3 for power circuit || 9 A at <= 440 V AC AC-3e for power circuit
- Auxiliary Contact Composition:
- 1 NC
- Mounting Support:
- plate || rail
- Auxiliary Contacts Type:
- instantaneous 1 NC
- Signaling Circuit Frequency:
- <= 400 Hz
- Operating Time:
- 10...20 ms coil energisation and NO closing || 10...20 ms coil de-energisation and NO opening
- Motor Power Kw:
- 2.2 kW 220...230 V AC 50/60 Hz || 4 kW 380...415 V AC 50/60 Hz || 4 kW 440 V AC 50/60 Hz || 4 kW 480 V AC 50/60 Hz || 4 kW 500...600 V AC 50/60 Hz || 4 kW 660...690 V AC 50/60 Hz
- Product Name:
- TeSys K
- Standards:
- EN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Ambient Air Temperature For Operation:
- -25-50°C
- [Ui] Rated Insulation Voltage:
- power circuit 600 V UL 508 || power circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-5-1 || Signaling circuit 600 V UL 508 || power circuit 600 V CSA C22.2 No 14 || Signaling circuit 600 V CSA