- Protective Treatment:
- TC IEC 60068 || TC DIN 50016
- Toxic Heavy Metal Free:
- Yes
- Average Impedance:
- 3 mOhm - Ith 20 A 50 Hz for power circuit
- [Icw] Rated Short-Time Withstand Current:
- 90 A 50°C - 1 s for power circuit || 85 A 50°C - 5 s for power circuit || 80 A 50°C - 10 s for power circuit || 60 A 50°C - 30 s for power circuit || 45 A 50°C - 1 min for power circuit || 40 A 50°C - 3 min for power circuit || 20 A 50°C - >= 15 min
- Non Overlap Distance:
- 0.5 mm
- Poles Description:
- 3P
- Weight:
- 0.39 kg
- [Ie] Rated Operational Current:
- 9 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 9 A (at <60°C) at <= 440 V AC AC-3e for power circuit || 20 A (at <60°C) at <= 690 V AC AC-1 for power circuit
- Maximum Operating Rate:
- 3600 cyc/h
- Ambient Air Temperature For Storage:
- -50-80°C
- Mechanical Durability:
- 5 Mcycles
- Rohs Exemption Information:
- Yes
- Contactor Application:
- motor control || resistive load
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Circularity Profile:
- ENVEOLI1503003EN
- Connections - Terminals:
- screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 mm²flexible with cable end || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 2 0.75-4
- Auxiliary Contact Composition:
- 1 NC
- Operating Altitude:
- 6561.68 ft (2000 m) without derating
- Flame Retardance:
- V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
- Warranty:
- 18 months
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Inrush Power In Va:
- 30-30 VA (at 20°C)
- Heat Dissipation:
- 1.3-1.3 W
- Motor Power Kw:
- 2.2 kW 220...230 V AC 50/60 Hz || 4 kW 380...415 V AC 50/60 Hz || 4 kW 440/690 V AC 50/60 Hz
- Product Or Component Type:
- reversing contactor
- Ip Degree Of Protection:
- IP20 VDE 0106
- [Ith] Conventional Free Air Thermal Current:
- 20 A (at 60°C) for power circuit || 10 A (at 50°C) for Signaling circuit
- Utilisation Category:
- AC-3 || AC-3e || AC-4 || AC-1
- Environmental Disclosure:
- ENVPEP1503003EN
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Sustainable Offer Status:
- Green Premium product
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Device Presentation:
- preassembled with reversing power busbar
- Signaling Circuit Frequency:
- <= 400 Hz
- Range:
- TeSys
- Device Short Name:
- LC2K
- Rated Breaking Capacity:
- 110 A at 220...230 V conforming to IEC 60947 || 110 A at 380...400 V conforming to IEC 60947 || 110 A at 415 V conforming to IEC 60947 || 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conformin
- Eu Rohs Directive:
- Compliant
- Depth:
- 57 mm
- Product Name:
- TeSys K
- [Ui] Rated Insulation Voltage:
- power circuit 600 V UL 508 || power circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-5-1 || Signaling circuit 600 V UL 508 || power circuit 600 V CSA C22.2 No 14 || Signaling circuit 600 V CSA
- Reach Free Of Svhc:
- Yes
- Height:
- 58 mm
- Tightening Torque:
- 0.8-1.3 N.m screw clamp terminals Philips No 2 || 0.8-1.3 N.m screw clamp terminals flat Ø 6 mm || 0.8-1.3 N.m screw clamp terminals pozidriv No 2
- Pole Contact Composition:
- 3 NO
- Country of Origin:
- France
- Electrical Durability:
- 1.3 Mcycles 9 A AC-3 <= 440 V || 1.3 Mcycles 9 A AC-3e <= 440 V || 0.16 Mcycles 20 A AC-1 <= 690 V || 0.02 Mcycles 54 A AC-4 <= 440 V