- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Toxic Heavy Metal Free:
- Yes
- Device Application:
- control
- Reach Free Of Svhc:
- Yes
- Circularity Profile:
- ENVEOLI1503003EN
- Environmental Disclosure:
- ENVPEP1503003EN
- Electrical Durability:
- 1.3 Mcycles 9 A AC-3 <= 440 V || 1.3 Mcycles 9 A AC-3e <= 440 V || 0.16 Mcycles 20 A AC-1 <= 690 V || 0.02 Mcycles 54 A AC-4 <= 440 V
- Ip Degree Of Protection:
- IP20 VDE 0106
- Height:
- 58 mm
- Contactor Application:
- resistive load || motor control
- Operating Time:
- 10...20 ms coil energisation and NO closing || 10...20 ms coil de-energisation and NO opening
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Interlocking Type:
- mechanical
- [Ith] Conventional Free Air Thermal Current:
- 20 A (at 50°C) for power circuit || 10 A (at 50°C) for Signaling circuit
- [Uc] Control Circuit Voltage:
- 120 V AC 50/60 Hz
- Auxiliary Contacts Type:
- instantaneous 1 NC
- Utilisation Category:
- AC-1 || AC-3 || AC-4 || AC-3e
- Motor Power Kw:
- 2.2 kW 220...230 V AC 50/60 Hz || 4 kW 380...415 V AC 50/60 Hz || 4 kW 440 V AC 50/60 Hz || 4 kW 480 V AC 50/60 Hz || 4 kW 500...600 V AC 50/60 Hz || 4 kW 660...690 V AC 50/60 Hz
- Irms Rated Making Capacity:
- 110 A AC for power circuit conforming to NF C 63-110 || 110 A AC for power circuit conforming to IEC 60947 || 110 A AC for Signaling circuit conforming to IEC 60947
- Maximum Operating Rate:
- 3600 cyc/h
- Rohs Exemption Information:
- Yes
- Protective Treatment:
- TC IEC 60068 || TC DIN 50016
- Inrush Power In Va:
- 30-30 VA (at 20°C)
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV
- Heat Dissipation:
- 1.3-1.3 W
- Standards:
- EN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1
- Operating Altitude:
- 6561.68 ft (2000 m) without derating
- Control Circuit Voltage Limits:
- operational: 0.8...1.15 Uc (at <50°C) || drop-out: 0.2...0.75 Uc (at <50°C)
- Product Name:
- TeSys K
- Hold-In Power Consumption In Va:
- 4.5-4.5 VA (at 20°C)
- Device Short Name:
- LC2K
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Mechanical Durability:
- 5 Mcycles
- [Ie] Rated Operational Current:
- 20 A (at <50°C) at <= 440 V AC AC-1 for power circuit || 16 A (at <70°C) at 690 V AC AC-1 for power circuit || 9 A at <= 440 V AC AC-3 for power circuit || 9 A at <= 440 V AC AC-3e for power circuit
- Weight:
- 0.39 kg
- Flame Retardance:
- V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
- [Ue] Rated Operational Voltage:
- power circuit 690 V AC 50/60 Hz || Signaling circuit <= 690 V AC 50/60 Hz
- Mercury Free:
- Yes
- Average Impedance:
- 3 mOhm - Ith 20 A 50 Hz for power circuit
- Poles Description:
- 3P
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Control Circuit Type:
- AC 50/60 Hz
- [Ui] Rated Insulation Voltage:
- power circuit 600 V UL 508 || power circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-5-1 || Signaling circuit 600 V UL 508 || power circuit 600 V CSA C22.2 No 14 || Signaling circuit 600 V CSA
- Ambient Air Temperature For Operation:
- -25-50°C
- Pole Contact Composition:
- 3 NO