Schneider Electric

Schneider Electric LC2K0910B7 Reversing contactor, TeSys K, 3P, AC-3, lt or eq to 440V 9A, 1 NO, 24VAC coil

(No reviews yet) Write a Review
SKU:
LC2K0910B7
MPN:
LC2K0910B7
Condition:
New
Overvoltage Category:
III
Ambient Air Temperature For Operation:
-25-50°C
Net Weight:
0.39 kg
Interlocking Type:
mechanical
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Circularity Profile:
ENVEOLI1503003EN
Product Certifications:
CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
Motor Power Kw:
2.2 kW 220...230 V AC 50/60 Hz || 4 kW 380...415 V AC 50/60 Hz || 4 kW 440/690 V AC 50/60 Hz
Maximum Operating Rate:
3600 cyc/h
Mechanical Durability:
5 Mcycles
Utilisation Category:
AC-3 || AC-3e || AC-4 || AC-1
Signaling Circuit Frequency:
<= 400 Hz
Product Or Component Type:
reversing contactor
Depth:
57 mm
Country of Origin:
France
[Icw] Rated Short-Time Withstand Current:
90 A 50°C - 1 s for power circuit || 85 A 50°C - 5 s for power circuit || 80 A 50°C - 10 s for power circuit || 60 A 50°C - 30 s for power circuit || 45 A 50°C - 1 min for power circuit || 40 A 50°C - 3 min for power circuit || 20 A 50°C - >= 15 min
Weight:
0.39 kg
Toxic Heavy Metal Free:
Yes
Average Impedance:
3 mOhm - Ith 20 A 50 Hz for power circuit
Poles Description:
3P
Operating Time:
10...20 ms coil energisation and NO closing || 10...20 ms coil de-energisation and NO opening
Inrush Power In Va:
30-30 VA (at 20°C)
Ambient Air Temperature For Storage:
-50-80°C
[Ie] Rated Operational Current:
9 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 9 A (at <60°C) at <= 440 V AC AC-3e for power circuit || 20 A (at <60°C) at <= 690 V AC AC-1 for power circuit
Reach Free Of Svhc:
Yes
Heat Dissipation:
1.3-1.3 W
[Ui] Rated Insulation Voltage:
power circuit 600 V UL 508 || power circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-5-1 || Signaling circuit 600 V UL 508 || power circuit 600 V CSA C22.2 No 14 || Signaling circuit 600 V CSA
Operating Altitude:
6561.68 ft (2000 m) without derating
Rohs Exemption Information:
Yes
Auxiliary Contact Composition:
1 NO
Non Overlap Distance:
0.5 mm
[Ith] Conventional Free Air Thermal Current:
20 A (at 60°C) for power circuit || 10 A (at 50°C) for Signaling circuit
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Insulation Resistance:
> 10 MOhm for Signaling circuit
Auxiliary Contacts Type:
instantaneous 1 NO
Protective Treatment:
TC IEC 60068 || TC DIN 50016
Device Presentation:
preassembled with reversing power busbar
Mercury Free:
Yes
Irms Rated Making Capacity:
110 A AC for power circuit conforming to IEC 60947 || 110 A AC for Signaling circuit conforming to IEC 60947
Flame Retardance:
V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
Device Short Name:
LC2K
Tightening Torque:
0.8-1.3 N.m screw clamp terminals Philips No 2 || 0.8-1.3 N.m screw clamp terminals flat Ø 6 mm || 0.8-1.3 N.m screw clamp terminals pozidriv No 2
Pole Contact Composition:
3 NO
Associated Fuse Rating:
25 A gG at <= 440 V for power circuit || 25 A aM for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947 || 10 A gG for Signaling circuit conforming to VDE 0660
Sustainable Offer Status:
Green Premium product
$167.00

Description

LC2K0910B7 is a compact 3-pole TeSys K reversing contactor from Schneider Electric for motor applications. Rated 9A AC-3 4kW@400V, it includes a 24V 50/60Hz AC coil, 2NO auxiliary contacts, a mechanical interlock and pre-wired reversing circuit. LC2K0910B7 is a 3-pole TeSys K reversing contactor from Schneider Electric for simple motor applications rated up to 4kW@400V. Very compact, DIN-rail compatible, with connections by screw clamp terminals, it is assembled with a mechanical interlock and a pre-wired reversing circuit. It includes a 24V 50/60Hz AC coil and 2NO built-in auxiliary contacts. Available worldwide, it complies with multi-standards (IEC, UL, CSA, CCC, EAC, Marine) and is certified Green Premium (RoHs/Reach). Very compact, 90mm wide, for DIN-rail and panel mounting. Assembled with mechanical interlock and pre-wired reversing circuit. Provides a 24V AC coil compatible 50/60Hz and 2NO built-in auxiliary contact. Can be completed with auxiliary contact blocks (LA1K, LA2K) and thermal relays (LR2K).