Schneider Electric

Schneider Electric LC2K1210G7 Reversing contactor, TeSys K, 3P, AC-3, lt or eq to 440V 12 A, 1 NO, 120VAC coil

(No reviews yet) Write a Review
SKU:
LC2K1210G7
MPN:
LC2K1210G7
Condition:
New
Net Weight:
0.39 kg
Country of Origin:
United States
Rohs Exemption Information:
Yes
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Reach Free Of Svhc:
Yes
Contactor Application:
resistive load || motor control
Minimum Switching Voltage:
17 V for Signaling circuit
Environmental Disclosure:
ENVPEP1503003EN
Auxiliary Contacts Type:
instantaneous 1 NO
Sustainable Offer Status:
Green Premium product
Circularity Profile:
ENVEOLI1503003EN
Control Circuit Type:
AC 50/60 Hz
Flame Retardance:
V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
Signaling Circuit Frequency:
<= 400 Hz
Toxic Heavy Metal Free:
Yes
Mechanical Robustness:
shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on X axis6 Gn for 11
Associated Fuse Rating:
25 A gG at <= 440 V for power circuit || 25 A aM for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947 || 10 A gG for Signaling circuit conforming to VDE 0660
Operating Time:
10...20 ms coil energisation and NO closing || 10...20 ms coil de-energisation and NO opening
Average Impedance:
3 mOhm - Ith 20 A 50 Hz for power circuit
Product Name:
TeSys K
Product Certifications:
CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Weight:
0.39 kg
Interlocking Type:
mechanical
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Tightening Torque:
0.8-1.3 N.m screw clamp terminals Philips No 2 || 0.8-1.3 N.m screw clamp terminals flat Ø 6 mm || 0.8-1.3 N.m screw clamp terminals pozidriv No 2
Ambient Air Temperature For Storage:
-50-80°C
[Ue] Rated Operational Voltage:
power circuit 690 V AC 50/60 Hz || Signaling circuit <= 690 V AC 50/60 Hz
Mechanical Durability:
5 Mcycles
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Depth:
57 mm
Maximum Operating Rate:
3600 cyc/h
Hold-In Power Consumption In Va:
4.5-4.5 VA (at 20°C)
Ip Degree Of Protection:
IP20 VDE 0106
Heat Dissipation:
1.3-1.3 W
Poles Description:
3P
Non Overlap Distance:
0.5 mm
Control Circuit Voltage Limits:
operational: 0.8...1.15 Uc (at <50°C) || drop-out: 0.2...0.75 Uc (at <50°C)
Device Presentation:
preassembled with reversing power busbar
Device Application:
control
Insulation Resistance:
> 10 MOhm for Signaling circuit
Eu Rohs Directive:
Compliant
Auxiliary Contact Composition:
1 NO
Mounting Support:
plate || rail
Mercury Free:
Yes
$191.00

Description

LC2K1210G7 is a compact 3-pole TeSys K reversing contactor from Schneider Electric for motor applications. Rated 12A AC-3 5.5kW@400V, it includes a 120V 50/60Hz AC coil, 2NO auxiliary contacts, a mechanical interlock and pre-wired reversing circuit. LC2K1210G7 is a 3-pole TeSys K reversing contactor from Schneider Electric for simple motor applications rated up to 5.5kW@400V. Very compact, DIN-rail compatible, with connections by screw clamp terminals, it is assembled with a mechanical interlock and a pre-wired reversing circuit. It includes a 120V 50/60Hz AC coil and 2NO built-in auxiliary contacts. Available worldwide, it complies with multi-standards (IEC, UL, CSA, CCC, EAC, Marine) and is certified Green Premium (RoHs/Reach). Very compact, 90mm wide, for DIN-rail and panel mounting. Assembled with mechanical interlock and pre-wired reversing circuit. Provides a 120V AC coil compatible 50/60Hz and 2NO built-in auxiliary contact. Can be completed with auxiliary contact blocks (LA1K, LA2K) and thermal relays (LR2K).
View AllClose