- Inrush Power In Va:
- 70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
- [Ie] Rated Operational Current:
- 32 A (at <60°C) at <= 440 V AC AC-3 for power circuit
- Operating Altitude:
- 9842.52 ft (3000 m) without derating
- Net Weight:
- 2.03 kg
- Environmental Disclosure:
- ENVPEP110229EN
- Maximum Operating Rate:
- 30 cyc/h 60°C
- Control Circuit Voltage Limits:
- drop-out: 0.3...0.6 Uc at 50/60 Hz (at <60°C) || operational: 0.8...1.1 Uc at 50 Hz (at <60°C) || operational: 0.85...1.1 Uc at 60 Hz (at <60°C)
- Product Name:
- TeSys Deca
- Eu Rohs Directive:
- Compliant
- Heat Dissipation:
- 2-3 W 50/60 Hz
- Warranty:
- 18 months
- Contactor Application:
- motor control
- Pole Contact Composition:
- 3 x 3 NO
- Country of Origin:
- France
- Device Presentation:
- pre-wired
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Fire Resistance:
- 850°C IEC 60695-2-1
- Hold-In Power Consumption In Va:
- 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
- Interlocking Type:
- mechanical
- Product Or Component Type:
- star delta starter
- Auxiliary Contact Composition:
- 1 NC KM1 star contactor
- Product Certifications:
- GOST || RINA || UL || CSA || BV || DNV || LROS (Lloyds register of shipping) || CCC || GL
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Protective Treatment:
- TH IEC 60068-2-30
- Mounting Support:
- plate
- Provided Equipment:
- protective cover
- Device Short Name:
- LC3D
- Climatic Withstand:
- IACS E10 || IEC 60947-1 Annex Q category D
- Poles Description:
- 3 x 3P
- Width:
- 166 mm
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Standards:
- EN 60947-4-1 || IEC 60947-5-1 || CSA C22.2 No 14 || EN 60947-5-1 || UL 508 || IEC 60947-4-1 || IEC 60335-1
- Weight:
- 2.03 kg
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Overvoltage Category:
- III
- Mechanical Robustness:
- vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open8 Gn for 11 ms
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Toxic Heavy Metal Free:
- Yes
- Ambient Air Temperature For Storage:
- -60-80°C
- Switching Voltage:
- 17 V Signaling circuit
- Electrical Durability:
- 1.65 Mcycles 32 A AC-3 <= 440 V
- Ambient Air Temperature For Operation:
- -40-70°C at Uc
- Depth:
- 149 mm
- Range:
- TeSys || TeSys Deca
- [Uc] Control Circuit Voltage:
- 230 V AC 50/60 Hz
- Pollution Degree:
- 3
- Coil Technology:
- without built-in suppressor module