Schneider Electric

Schneider Electric LDA36400U54X Circuit breaker, PowerPacT L, 400A, 3 pole, 600VAC, 14kA, I-Line, MicroLogic 6.3E, 80%, ABC

(No reviews yet) Write a Review
SKU:
LDA36400U54X
MPN:
LDA36400U54X
Condition:
New
Trip Unit Name:
MicroLogic 6.3 E
Electrical Connection:
I-Line connection, line || lugs, load
Continuous Current Rating:
0.8
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Depth:
110 mm
Protection Technology:
current limiter
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Line Rated Current:
400-400 A
Tightening Torque:
50-50 N.m 95-240 mm² (AWG 3/0...500 kcmil)
Range:
PowerPact
Breaking Capacity Code:
D
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Mounting Height:
6 in
Terminal Identifier:
AL600LF52K3
Phase Connection:
ABC
Warranty:
18 months
Ambient Air Temperature For Operation:
-25-70°C
Product Or Component Type:
circuit breaker
Control Type:
toggle
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Poles Description:
3P
Circularity Profile:
ENVEOLI2206029EN
Mercury Free:
Yes
Ip Degree Of Protection:
front cover IP40
Net Weight:
6.2 kg
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Weight:
6.2 kg
[Ics] Rated Service Breaking Capacity:
25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Environmental Disclosure:
ENVPEP2206029EN
Length:
31 mm
Product Name:
PowerPact L
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz IEC 60947-3
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Circuit Breaker Application:
HACR rated
Rohs Exemption Information:
Yes
Suitability For Isolation:
yes IEC 60947-2
Height:
6 in
Network Frequency:
50/60 Hz
Pollution Degree:
3 IEC 60947-1
Country of Origin:
United States
Awg Gauge:
AWG 3/0...500 kcmil aluminium/copper
Local Signaling:
ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
Device Short Name:
L-Frame
Mounting Support:
bracket
Trip Unit Technology:
electronic, energy, MicroLogic 6.3 E, LSIG
Breaking Capacity:
25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz UL 489 || 14 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
$9,392.00

Description

PowerPacT L-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT L-Frame circuit breakers are available with electronic trip units. All PowerPacT L-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT L circuit breakers are available in 3 and 4-pole unit mount, I-Line, and drawout constructions. This PowerPacT L, 400A, 3 pole, circuit breaker has an interrupting rating of 14kA at 600VAC. This circuit breaker provides MicroLogic Energy with a 6.3E trip unit and an LSIG function. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose