Schneider Electric

Schneider Electric LGA36600U44X Circuit breaker, PowerPacT L, 600A, 3 pole, 600VAC, 18kA, I-Line, MicroLogic 6.3A, 80%, ABC

(No reviews yet) Write a Review
SKU:
LGA36600U44X
MPN:
LGA36600U44X
Condition:
New
Continuous Current Rating:
0.8
Weight:
6.2 kg
Ambient Air Temperature For Storage:
-50-85°C
Net Weight:
6.2 kg
Product Name:
PowerPact L
Environmental Disclosure:
ENVPEP2206029EN
Communication Interface:
Modbus || Ethernet
Height:
340 mm
Electrical Connection:
I-Line connection, line || lugs, load
Trip Unit Technology:
electronic, ammeter, MicroLogic 6.3 A, LSIG
Tightening Torque:
50-50 N.m 70-240 mm² (2 x AWG 2/0...500 kcmil)
Sustainable Offer Status:
Green Premium product
Suitability For Isolation:
yes IEC 60947-2
Utilisation Category:
category A
Line Rated Current:
600-600 A
Mounting Height:
6 in
Pollution Degree:
3 IEC 60947-1
Local Signaling:
ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
Circularity Profile:
ENVEOLI2206029EN
Awg Gauge:
2 x AWG 2/0...500 kcmil aluminium/copper
Pvc Free:
Yes
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Wire Stripping Length:
31 mm
Mercury Free:
Yes
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Mounting Support:
bracket
Phase Connection:
ABC
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Country of Origin:
Mexico
Depth:
110 mm
Breaking Capacity Code:
G
Device Application:
distribution
Mounting Mode:
I-Line bracket)
Warranty:
18 months
Ambient Air Temperature For Operation:
-25-70°C
Trip Unit Name:
MicroLogic 6.3 A
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz IEC 60947-3
Breaking Capacity:
65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Rohs Exemption Information:
Yes
Product Certifications:
UL || CSA || NOM
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Device Short Name:
L-Frame
Ip Degree Of Protection:
front cover IP40
Color:
Black
Control Type:
toggle
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Network Frequency:
50/60 Hz
$11,275.00

Description

PowerPacT L-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT L-Frame circuit breakers are available with electronic trip units. All PowerPacT L-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT L circuit breakers are available in 3 and 4-pole unit mount, I-Line, and drawout constructions. This PowerPacT L, 600A, 3 pole, circuit breaker has an interrupting rating of 18kA at 600VAC. This circuit breaker provides MicroLogic Ammeter with a 6.3A trip unit and an LSIG function. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose