Schneider Electric

Schneider Electric LLA36400CU33X Circuit breaker, PowerPacT L, 400A, 3 pole, 600VAC, 50kA, I-Line, MicroLogic 3.3S, 100%, ABC

(No reviews yet) Write a Review
SKU:
LLA36400CU33X
MPN:
LLA36400CU33X
Condition:
New
Awg Gauge:
2 x AWG 2/0...500 kcmil aluminium/copper
Product Or Component Type:
circuit breaker
Warranty:
18 months
Pvc Free:
Yes
Height:
340 mm
Protection Technology:
current limiter
Phase Connection:
ABC
Device Application:
distribution
Mounting Support:
bracket
Country of Origin:
United States
Terminal Identifier:
AL600LS52K3
Poles Description:
3P
Communication Interface:
Modbus || Ethernet
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Tightening Torque:
50-50 N.m 70-240 mm² (AWG 2/0...500 kcmil)
Trip Unit Technology:
electronic, standard, MicroLogic 3.3 S, LSI
Line Rated Current:
400-400 A
Product Certifications:
UL || CSA || NOM
Pollution Degree:
3 IEC 60947-1
Length:
31 mm
Utilisation Category:
category A
Height:
6 in
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Product Name:
PowerPact L
Long Time Pick-Up Adjustment Range:
0.25...1 x In
Ip Degree Of Protection:
front cover IP40
Continuous Current Rating:
1
Circularity Profile:
ENVEOLI2206029EN
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Breaking Capacity Code:
L
Color:
Black
Control Type:
toggle
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz IEC 60947-3
Local Signaling:
ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
Net Weight:
6.2 kg
Ambient Air Temperature For Storage:
-50-85°C
Range:
PowerPact
Mounting Mode:
I-Line bracket)
Depth:
110 mm
Device Short Name:
L-Frame
Ambient Air Temperature For Operation:
-25-70°C
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Sustainable Offer Status:
Green Premium product
Electrical Connection:
I-Line connection, line || lugs, load
Trip Unit Name:
MicroLogic 3.3 S
$12,493.00

Description

PowerPacT L-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT L-Frame circuit breakers are available with electronic trip units. All PowerPacT L-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT L circuit breakers are available in 3 and 4-pole unit mount, I-Line, and drawout constructions. This PowerPacT L, 400A, 3 pole, circuit breaker has an interrupting rating of 50kA at 600VAC. This circuit breaker provides MicroLogic Standard with a 3.3S trip unit and an LSI function. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This circuit breaker has a continuous current rating of 100% with an ABC phase connection. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.