Schneider Electric LP1D80008ED IEC contactor, TeSys Deca, nonreversing, 125A resistive, 4 pole, 2 NO and 2 NC, 48VDC coil, open style
Schneider Electric
$599.00
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 125A resistive load rating. Contactor is supplied with a 48 VDC coil. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.78 inches wide and 7.72 inches deep. It weighs 6.42 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Environmental Disclosure:
- ENVPEP110205EN
- Control Circuit Voltage Limits:
- 0.1...0.3 Uc -40-55°C drop-out DC || 0.85...1.1 Uc -40-55°C operational DC
- Mounting Support:
- plate || rail
- Range Of Product:
- TeSys Deca
- Operating Time:
- 6...20 ms opening || 20...35 ms closing
- Protective Cover:
- without
- Width:
- 96 mm
- Connections - Terminals:
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-2.5 mm²
- Rated Breaking Capacity:
- 1100 A at 440 V for power circuit conforming to IEC 60947
- Product Certifications:
- UL || CSA || CCC || EAC || UKCA || CB || DNV-GL || RINA || BV || LROS (Lloyds register of shipping)
- Pole Contact Composition:
- 2 NO + 2 NC
- Mechanical Durability:
- 10 Mcycles
- Contactor Application:
- resistive load
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Compatibility Code:
- LP1D
- Mechanical Robustness:
- vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 3 Gn, 5...300 Hz) || shocks contactor open 8 Gn for 11 ms) || shocks contactor closed 10 Gn for 11 ms)
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
- Fire Resistance:
- 850°C IEC 60695-2-1
- [Ith] Conventional Free Air Thermal Current:
- 125 A (at 60°C) for power circuit
- Control Circuit Type:
- DC DC standard
- Net Weight:
- 2.91 kg
- Coil Technology:
- without built-in suppressor module
- Range:
- TeSys
- Power Dissipation Per Pole:
- 12.5 W AC-1
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Mercury Free:
- Yes
- Average Impedance:
- 0.8 mOhm - Ith 125 A 50 Hz for power circuit
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Overvoltage Category:
- III
- Device Short Name:
- LP1D
- Hold-In Power Consumption In W:
- 22-22 W 20°C
- Pollution Degree:
- 3
- Utilisation Category:
- AC-1
- Flame Retardance:
- V1 conforming to UL 94
- Eu Rohs Directive:
- Compliant
- [Ie] Rated Operational Current:
- 125 A (at <60°C) at <= 440 V AC AC-1 for power circuit
- Rohs Exemption Information:
- Yes
- Irms Rated Making Capacity:
- 1100 A at 440 V for power circuit conforming to IEC 60947
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Associated Fuse Rating:
- 200 A gG at <= 690 V coordination type 1 for power circuit || 160 A gG at <= 690 V coordination type 2 for power circuit
- Depth:
- 196 mm
- Inrush Power In W:
- 22-22 W 20°C)
- [Ui] Rated Insulation Voltage:
- power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1
- Tightening Torque:
- control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector flat Ø 6 to Ø 8 mm || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947
- [Uc] Control Circuit Voltage:
- 48 V DC