- Motor Power Kw:
- 1.5 kW 220...230 V AC 50/60 Hz AC-3 || 2.2 kW 380...415 V AC 50/60 Hz AC-3 || 3 kW 440/690 V AC 50/60 Hz AC-3 || 1.5 kW 220...230 V AC 50/60 Hz AC-3e || 2.2 kW 380...415 V AC 50/60 Hz AC-3e || 3 kW 440/690 V AC 50/60 Hz AC-3e || 1.5 kW 220...230 V AC
- Rated Breaking Capacity:
- 110 A at 220...230 V conforming to IEC 60947 || 110 A at 380...400 V conforming to IEC 60947 || 110 A at 415 V conforming to IEC 60947 || 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conformin
- Control Circuit Voltage Limits:
- operational: 0.8...1.15 Uc (at <50°C) || drop-out: >= 0.10 Uc (at <50°C)
- Circularity Profile:
- ENVEOLI1503003EN
- Toxic Heavy Metal Free:
- Yes
- [Icw] Rated Short-Time Withstand Current:
- 90 A 50°C - 1 s for power circuit || 85 A 50°C - 5 s for power circuit || 80 A 50°C - 10 s for power circuit || 60 A 50°C - 30 s for power circuit || 45 A 50°C - 1 min for power circuit || 40 A 50°C - 3 min for power circuit || 20 A 50°C - >= 15 min
- [Ui] Rated Insulation Voltage:
- power circuit 600 V UL 508 || power circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-5-1 || Signaling circuit 600 V UL 508 || power circuit 600 V CSA C22.2 No 14 || Signaling circuit 600 V CSA
- Pole Contact Composition:
- 3 NO
- Contactor Application:
- motor control
- Sustainable Offer Status:
- Green Premium product
- Inrush Power In W:
- 3-3 W 20°C)
- Mercury Free:
- Yes
- Hold-In Power Consumption In W:
- 3-3 W 20°C
- Product Or Component Type:
- contactor
- Control Circuit Type:
- DC standard
- Device Short Name:
- LP1K
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Rohs Exemption Information:
- Yes
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Net Weight:
- 0.225 kg
- Utilisation Category:
- AC-3 || AC-3e || AC-4
- Electrical Durability:
- 1.3 Mcycles 6 A AC-3 <= 440 V || 1.3 Mcycles 6 A AC-3e <= 440 V || 0.05 Mcycles 36 A AC-4 <= 440 V
- Mounting Support:
- rail || plate
- Eu Rohs Directive:
- Compliant
- Maximum Operating Rate:
- 3600 cyc/h
- Reach Free Of Svhc:
- Yes
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC <= 400 Hz || Signaling circuit <= 690 V AC <= 400 Hz
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV
- Poles Description:
- 3P
- [Uc] Control Circuit Voltage:
- 110 V DC
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Auxiliary Contact Composition:
- 1 NO
- Country of Origin:
- Indonesia
- Ip Degree Of Protection:
- IP2X
- Overvoltage Category:
- III
- Standards:
- EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4
- Mechanical Durability:
- 10 Mcycles
- Auxiliary Contacts Type:
- instantaneous 1 NO
- Heat Dissipation:
- 1.3-1.3 W
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Tightening Torque:
- 0.8-1.3 N.m screw clamp terminals Philips No 2 || 0.8-1.3 N.m screw clamp terminals flat Ø 6 mm || 0.8-1.3 N.m screw clamp terminals pozidriv No 2
- Associated Fuse Rating:
- 25 A gG at <= 440 V for power circuit || 25 A aM for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947 || 10 A gG for Signaling circuit conforming to VDE 0660
- Environmental Disclosure:
- ENVPEP1503003EN
- Average Impedance:
- 3 mOhm - Ith 20 A 50 Hz for power circuit
- Product Certifications:
- CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
- Warranty:
- 18 months