Schneider Electric

Schneider Electric LP1K09008MD Contactor, TeSys K, 4P, 2 NO + 2 NC, AC-1, lt or eq to 440V, 20A, 220VDC coil

(No reviews yet) Write a Review
SKU:
LP1K09008MD
MPN:
LP1K09008MD
Condition:
New
Mechanical Durability:
10 Mcycles
Sustainable Offer Status:
Green Premium product
Device Short Name:
LP1K
Flame Retardance:
V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
Operating Altitude:
6561.68 ft (2000 m) without derating
[Ie] Rated Operational Current:
20 A (at <60°C) at <= 690 V AC AC-1 for power circuit
Range:
TeSys
Product Certifications:
CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
Ambient Air Temperature For Operation:
-25-50°C
[Icw] Rated Short-Time Withstand Current:
90 A 50°C - 1 s for power circuit || 85 A 50°C - 5 s for power circuit || 80 A 50°C - 10 s for power circuit || 60 A 50°C - 30 s for power circuit || 45 A 50°C - 1 min for power circuit || 40 A 50°C - 3 min for power circuit || 20 A 50°C - >= 15 min
Tightening Torque:
0.8-1.3 N.m screw clamp terminals Philips No 2 || 0.8-1.3 N.m screw clamp terminals flat Ø 6 mm || 0.8-1.3 N.m screw clamp terminals pozidriv No 2
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Circularity Profile:
ENVEOLI1503003EN
Pole Contact Composition:
2 NO + 2 NC
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Associated Fuse Rating:
25 A gG at <= 440 V for power circuit || 25 A aM for power circuit
Net Weight:
0.225 kg
Electrical Durability:
0.16 Mcycles 20 A AC-1 <= 690 V
Hold-In Power Consumption In W:
3-3 W 20°C
Operating Time:
30...40 ms coil energisation and NO closing || 10 ms coil de-energisation and NO opening || 25...35 ms coil energisation and NC opening || 15 ms coil de-energisation and NC closing
Toxic Heavy Metal Free:
Yes
[Ui] Rated Insulation Voltage:
power circuit 600 V UL 508 || power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA C22.2 No 14
Overvoltage Category:
III
Contactor Application:
resistive load
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Control Circuit Type:
DC standard
Utilisation Category:
AC-1
Poles Description:
4P
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC <= 400 Hz || Signaling circuit <= 690 V AC <= 400 Hz
Country of Origin:
Indonesia
[Uc] Control Circuit Voltage:
220 V DC
Maximum Operating Rate:
3600 cyc/h
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Mercury Free:
Yes
[Ith] Conventional Free Air Thermal Current:
20 A (at 60°C) for power circuit || 10 A (at 50°C) for Signaling circuit
Mounting Support:
rail || plate
Depth:
57 mm
Reach Free Of Svhc:
Yes
Warranty:
18 months
Heat Dissipation:
1.3-1.3 W
Irms Rated Making Capacity:
110 A AC for power circuit conforming to IEC 60947
Product Or Component Type:
contactor
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4
Ambient Air Temperature For Storage:
-50-80°C
Reach Regulation:
Free of Substances of Very High Concern above the threshold
$98.00

Description

TeSys K contactor, 4 poles (2NO+2NC), for non-inductive load control applications up to 20A/690V AC-1. It provides a 220V DC coil, without built-in auxiliary contact, connection by screw clamp terminals. For operating rates until 600 cycles/hour and environments until 50°C, it procures reliability and durability to standard applications. Very compact (45mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).