Schneider Electric LP1K09008MD Contactor, TeSys K, 4P, 2 NO + 2 NC, AC-1, lt or eq to 440V, 20A, 220VDC coil
Schneider Electric
$98.00
TeSys K contactor, 4 poles (2NO+2NC), for non-inductive load control applications up to 20A/690V AC-1. It provides a 220V DC coil, without built-in auxiliary contact, connection by screw clamp terminals. For operating rates until 600 cycles/hour and environments until 50°C, it procures reliability and durability to standard applications. Very compact (45mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
- Mechanical Durability:
- 10 Mcycles
- Sustainable Offer Status:
- Green Premium product
- Device Short Name:
- LP1K
- Flame Retardance:
- V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
- Operating Altitude:
- 6561.68 ft (2000 m) without derating
- [Ie] Rated Operational Current:
- 20 A (at <60°C) at <= 690 V AC AC-1 for power circuit
- Range:
- TeSys
- Product Certifications:
- CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
- Ambient Air Temperature For Operation:
- -25-50°C
- [Icw] Rated Short-Time Withstand Current:
- 90 A 50°C - 1 s for power circuit || 85 A 50°C - 5 s for power circuit || 80 A 50°C - 10 s for power circuit || 60 A 50°C - 30 s for power circuit || 45 A 50°C - 1 min for power circuit || 40 A 50°C - 3 min for power circuit || 20 A 50°C - >= 15 min
- Tightening Torque:
- 0.8-1.3 N.m screw clamp terminals Philips No 2 || 0.8-1.3 N.m screw clamp terminals flat Ø 6 mm || 0.8-1.3 N.m screw clamp terminals pozidriv No 2
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Circularity Profile:
- ENVEOLI1503003EN
- Pole Contact Composition:
- 2 NO + 2 NC
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Associated Fuse Rating:
- 25 A gG at <= 440 V for power circuit || 25 A aM for power circuit
- Net Weight:
- 0.225 kg
- Electrical Durability:
- 0.16 Mcycles 20 A AC-1 <= 690 V
- Hold-In Power Consumption In W:
- 3-3 W 20°C
- Operating Time:
- 30...40 ms coil energisation and NO closing || 10 ms coil de-energisation and NO opening || 25...35 ms coil energisation and NC opening || 15 ms coil de-energisation and NC closing
- Toxic Heavy Metal Free:
- Yes
- [Ui] Rated Insulation Voltage:
- power circuit 600 V UL 508 || power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA C22.2 No 14
- Overvoltage Category:
- III
- Contactor Application:
- resistive load
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Control Circuit Type:
- DC standard
- Utilisation Category:
- AC-1
- Poles Description:
- 4P
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC <= 400 Hz || Signaling circuit <= 690 V AC <= 400 Hz
- Country of Origin:
- Indonesia
- [Uc] Control Circuit Voltage:
- 220 V DC
- Maximum Operating Rate:
- 3600 cyc/h
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV
- Mercury Free:
- Yes
- [Ith] Conventional Free Air Thermal Current:
- 20 A (at 60°C) for power circuit || 10 A (at 50°C) for Signaling circuit
- Mounting Support:
- rail || plate
- Depth:
- 57 mm
- Reach Free Of Svhc:
- Yes
- Warranty:
- 18 months
- Heat Dissipation:
- 1.3-1.3 W
- Irms Rated Making Capacity:
- 110 A AC for power circuit conforming to IEC 60947
- Product Or Component Type:
- contactor
- Standards:
- EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4
- Ambient Air Temperature For Storage:
- -50-80°C
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold