- Product Certifications:
- CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
- [Icw] Rated Short-Time Withstand Current:
- 90 A 50°C - 1 s for power circuit || 85 A 50°C - 5 s for power circuit || 80 A 50°C - 10 s for power circuit || 60 A 50°C - 30 s for power circuit || 45 A 50°C - 1 min for power circuit || 40 A 50°C - 3 min for power circuit || 20 A 50°C - >= 15 min
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV
- [Ith] Conventional Free Air Thermal Current:
- 16 A (at 60°C) for power circuit || 10 A (at 50°C) for Signaling circuit
- Electrical Durability:
- 1.3 Mcycles 9 A AC-3 <= 440 V || 1.3 Mcycles 9 A AC-3e <= 440 V || 0.16 Mcycles 20 A AC-1 <= 690 V || 0.02 Mcycles 54 A AC-4 <= 440 V
- Ip Degree Of Protection:
- IP2X
- Connections - Terminals:
- spring terminals 1 0.75-1.5 mm²solid || spring terminals 1 0.75-1.5 mm²flexible without cable end || spring terminals 2 0.75-1.5 mm²flexible without cable end
- Irms Rated Making Capacity:
- 110 A AC for power circuit conforming to IEC 60947 || 110 A AC for Signaling circuit conforming to IEC 60947
- Ambient Air Temperature For Storage:
- -50-80°C
- Weight:
- 0.225 kg
- Product Or Component Type:
- contactor
- Control Circuit Voltage Limits:
- operational: 0.8...1.15 Uc (at <50°C) || drop-out: >= 0.10 Uc (at <50°C)
- [Ui] Rated Insulation Voltage:
- power circuit 600 V UL 508 || power circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-5-1 || Signaling circuit 600 V UL 508 || power circuit 600 V CSA C22.2 No 14 || Signaling circuit 600 V CSA
- Associated Fuse Rating:
- 25 A gG at <= 440 V for power circuit || 25 A aM for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947 || 10 A gG for Signaling circuit conforming to VDE 0660
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Coil Technology:
- built-in bidirectional peak limiting diode suppressor
- Ambient Air Temperature For Operation:
- -25-50°C
- Motor Power Kw:
- 2.2 kW 220...230 V AC 50/60 Hz AC-3 || 4 kW 380...415 V AC 50/60 Hz AC-3 || 4 kW 440/690 V AC 50/60 Hz AC-3 || 2.2 kW 220...230 V AC 50/60 Hz AC-3e || 4 kW 380...415 V AC 50/60 Hz AC-3e || 4 kW 440/690 V AC 50/60 Hz AC-3e || 2.2 kW 220...230 V AC 50/
- Country of Origin:
- France
- Average Impedance:
- 3 mOhm - Ith 16 A 50 Hz for power circuit
- Auxiliary Contacts Type:
- instantaneous 1 NC
- Contactor Application:
- motor control || resistive load
- Environmental Disclosure:
- ENVPEP1503003EN
- [Ie] Rated Operational Current:
- 9 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 9 A (at <60°C) at <= 440 V AC AC-3e for power circuit || 20 A (at <60°C) at <= 690 V AC AC-1 for power circuit
- Control Circuit Type:
- DC standard
- Reach Free Of Svhc:
- Yes
- Device Short Name:
- LP1K
- Depth:
- 57 mm
- Mounting Support:
- plate || rail
- Pole Contact Composition:
- 3 NO
- Utilisation Category:
- AC-3 || AC-3e || AC-1 || AC-4
- Poles Description:
- 3P
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC <= 400 Hz || Signaling circuit <= 690 V AC <= 400 Hz
- Heat Dissipation:
- 1.3-1.3 W
- [Uc] Control Circuit Voltage:
- 24 V DC
- Toxic Heavy Metal Free:
- Yes
- Hold-In Power Consumption In W:
- 3-3 W 20°C
- Mechanical Durability:
- 10 Mcycles
- Inrush Power In W:
- 3-3 W 20°C)
- Overvoltage Category:
- III
- Maximum Operating Rate:
- 3600 cyc/h
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Mercury Free:
- Yes
- Minimum Switching Current:
- 5 mA for Signaling circuit
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)