Schneider Electric

Schneider Electric LP1K0910ED Contactor, TeSys K, 3P, AC-3, lt or eq to 440V, 9A, 1 NO aux, 48VDC coil

(No reviews yet) Write a Review
SKU:
LP1K0910ED
MPN:
LP1K0910ED
Condition:
New
Mounting Support:
plate || rail
Pole Contact Composition:
3 NO
Minimum Switching Current:
5 mA for Signaling circuit
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Utilisation Category:
AC-3 || AC-3e || AC-1 || AC-4
[Ie] Rated Operational Current:
9 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 9 A (at <60°C) at <= 440 V AC AC-3e for power circuit || 20 A (at <60°C) at <= 690 V AC AC-1 for power circuit
Hold-In Power Consumption In W:
3-3 W 20°C
Net Weight:
0.225 kg
Rohs Exemption Information:
Yes
Maximum Operating Rate:
3600 cyc/h
Operating Altitude:
6561.68 ft (2000 m) without derating
Mechanical Durability:
10 Mcycles
Depth:
57 mm
Average Impedance:
3 mOhm - Ith 20 A 50 Hz for power circuit
Ambient Air Temperature For Operation:
-25-50°C
Operating Time:
30...40 ms coil energisation and NO closing || 10 ms coil de-energisation and NO opening
Irms Rated Making Capacity:
110 A AC for power circuit conforming to IEC 60947 || 110 A AC for Signaling circuit conforming to IEC 60947
Mercury Free:
Yes
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4
Poles Description:
3P
Environmental Disclosure:
ENVPEP1503003EN
Control Circuit Voltage Limits:
operational: 0.8...1.15 Uc (at <50°C) || drop-out: >= 0.10 Uc (at <50°C)
Weight:
0.225 kg
Product Or Component Type:
contactor
Country of Origin:
Indonesia
Overvoltage Category:
III
Eu Rohs Directive:
Compliant
Circularity Profile:
ENVEOLI1503003EN
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Product Certifications:
CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Tightening Torque:
0.8-1.3 N.m screw clamp terminals Philips No 2 || 0.8-1.3 N.m screw clamp terminals flat Ø 6 mm || 0.8-1.3 N.m screw clamp terminals pozidriv No 2
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Electrical Durability:
1.3 Mcycles 9 A AC-3 <= 440 V || 1.3 Mcycles 9 A AC-3e <= 440 V || 0.16 Mcycles 20 A AC-1 <= 690 V || 0.02 Mcycles 54 A AC-4 <= 440 V
Ip Degree Of Protection:
IP2X
Height:
58 mm
Heat Dissipation:
1.3-1.3 W
Auxiliary Contact Composition:
1 NO
Range:
TeSys
Motor Power Kw:
2.2 kW 220...230 V AC 50/60 Hz AC-3 || 4 kW 380...415 V AC 50/60 Hz AC-3 || 4 kW 440/690 V AC 50/60 Hz AC-3 || 2.2 kW 220...230 V AC 50/60 Hz AC-3e || 4 kW 380...415 V AC 50/60 Hz AC-3e || 4 kW 440/690 V AC 50/60 Hz AC-3e || 2.2 kW 220...230 V AC 50/
Contactor Application:
resistive load || motor control
Ambient Air Temperature For Storage:
-50-80°C
Connections - Terminals:
screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 mm²flexible with cable end || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 2 0.75-4
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC <= 400 Hz || Signaling circuit <= 690 V AC <= 400 Hz
Reach Free Of Svhc:
Yes
Insulation Resistance:
> 10 MOhm for Signaling circuit
Rated Breaking Capacity:
110 A at 220...230 V conforming to IEC 60947 || 110 A at 380...400 V conforming to IEC 60947 || 110 A at 415 V conforming to IEC 60947 || 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conformin
$92.00

Description

LP1K0910ED is a compact 3-pole TeSys K contactor from Schneider Electric for motor applications. Rated 9A AC-3 4kW@400V, it includes a 48 V DC coil and 1NO auxiliary contact allowing easy integration to all control systems. LP1K0910ED is a 3-pole TeSys K contactor from Schneider Electric for simple motor applications rated up to 4kW@400V. Very compact, DIN-rail compatible, with connections by screw clamp terminals, it can be easily integrated into all control systems thanks to its 48V DC coil and 1NO built-in auxiliary contact. Available worldwide, it complies with multi-standards (IEC, UL, CSA, CCC, EAC, Marine) and is certified Green Premium (RoHs/Reach). Very compact, 45mm wide, for DIN-rail and panel mounting. Ready for connection to all control systems thanks to a 48V DC control voltage and 1NO built-in auxiliary contact. Optimized for simple power applications. Can be completed with auxiliary contact blocks (LA1K, LA2K) and thermal relays (LR2K).