- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Overvoltage Category:
- III
- Average Impedance:
- 3 mOhm - Ith 20 A 50 Hz for power circuit
- Ambient Air Temperature For Storage:
- -50-80°C
- [Uc] Control Circuit Voltage:
- 110 V DC
- Standards:
- EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4
- Control Circuit Type:
- DC standard
- [Icw] Rated Short-Time Withstand Current:
- 90 A 50°C - 1 s for power circuit || 85 A 50°C - 5 s for power circuit || 80 A 50°C - 10 s for power circuit || 60 A 50°C - 30 s for power circuit || 45 A 50°C - 1 min for power circuit || 40 A 50°C - 3 min for power circuit || 20 A 50°C - >= 15 min
- Maximum Operating Rate:
- 3600 cyc/h
- Weight:
- 0.225 kg
- Flame Retardance:
- V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
- Utilisation Category:
- AC-3 || AC-3e || AC-1 || AC-4
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Rohs Exemption Information:
- Yes
- Depth:
- 57 mm
- [Ith] Conventional Free Air Thermal Current:
- 20 A (at 60°C) for power circuit || 10 A (at 50°C) for Signaling circuit
- Hold-In Power Consumption In W:
- 3-3 W 20°C
- Pole Contact Composition:
- 3 NO
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Electrical Durability:
- 1.3 Mcycles 9 A AC-3 <= 440 V || 1.3 Mcycles 9 A AC-3e <= 440 V || 0.16 Mcycles 20 A AC-1 <= 690 V || 0.02 Mcycles 54 A AC-4 <= 440 V
- Product Or Component Type:
- contactor
- Range:
- TeSys
- Mounting Support:
- rail || plate
- Ip Degree Of Protection:
- IP2X
- Mechanical Durability:
- 10 Mcycles
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV
- Auxiliary Contact Composition:
- 1 NO
- Auxiliary Contacts Type:
- instantaneous 1 NO
- Country of Origin:
- Indonesia
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Poles Description:
- 3P
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC <= 400 Hz || Signaling circuit <= 690 V AC <= 400 Hz
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Operating Altitude:
- 6561.68 ft (2000 m) without derating
- Heat Dissipation:
- 1.3-1.3 W
- Contactor Application:
- motor control || resistive load
- Inrush Power In W:
- 3-3 W 20°C)
- Device Short Name:
- LP1K
- Control Circuit Voltage Limits:
- operational: 0.8...1.15 Uc (at <50°C) || drop-out: >= 0.10 Uc (at <50°C)
- Circularity Profile:
- ENVEOLI1503003EN
- Rated Breaking Capacity:
- 110 A at 220...230 V conforming to IEC 60947 || 110 A at 380...400 V conforming to IEC 60947 || 110 A at 415 V conforming to IEC 60947 || 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conformin
- Ambient Air Temperature For Operation:
- -25-50°C
- Motor Power Kw:
- 2.2 kW 220...230 V AC 50/60 Hz AC-3 || 4 kW 380...415 V AC 50/60 Hz AC-3 || 4 kW 440/690 V AC 50/60 Hz AC-3 || 2.2 kW 220...230 V AC 50/60 Hz AC-3e || 4 kW 380...415 V AC 50/60 Hz AC-3e || 4 kW 440/690 V AC 50/60 Hz AC-3e || 2.2 kW 220...230 V AC 50/
- Environmental Disclosure:
- ENVPEP1503003EN
- [Ie] Rated Operational Current:
- 9 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 9 A (at <60°C) at <= 440 V AC AC-3e for power circuit || 20 A (at <60°C) at <= 690 V AC AC-1 for power circuit