- Hold-In Power Consumption In W:
- 3-3 W 20°C
- Depth:
- 57 mm
- Flame Retardance:
- V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
- Electrical Durability:
- 1.3 Mcycles 12 A AC-3 <= 440 V || 1.3 Mcycles 12 A AC-3e <= 440 V || 0.3 Mcycles 20 A AC-1 <= 690 V || 0.02 Mcycles 72 A AC-4 <= 440 V
- Warranty:
- 18 months
- Contactor Application:
- motor control || resistive load
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Motor Power Kw:
- 3 kW 220...230 V AC 50/60 Hz AC-3 || 5.5 kW 380...415 V AC 50/60 Hz AC-3 || 5.5 kW 440 V AC 50/60 Hz AC-3 || 4 kW 690 V AC 50/60 Hz AC-3 || 3 kW 220...230 V AC 50/60 Hz AC-3e || 5.5 kW 380...415 V AC 50/60 Hz AC-3e || 5.5 kW 440 V AC 50/60 Hz AC-3e |
- Heat Dissipation:
- 1.3-1.3 W
- Reach Free Of Svhc:
- Yes
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV
- Utilisation Category:
- AC-3 || AC-3e || AC-1 || AC-4
- Height:
- 58 mm
- Average Impedance:
- 3 mOhm - Ith 20 A 50 Hz for power circuit
- Sustainable Offer Status:
- Green Premium product
- Mercury Free:
- Yes
- Operating Altitude:
- 6561.68 ft (2000 m) without derating
- Weight:
- 0.225 kg
- Circularity Profile:
- ENVEOLI1503003EN
- Device Short Name:
- LP1K
- Ambient Air Temperature For Storage:
- -50-80°C
- Rated Breaking Capacity:
- 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conforming to IEC 60947
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Auxiliary Contact Composition:
- 1 NC
- Environmental Disclosure:
- ENVPEP1503003EN
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Mounting Support:
- plate || rail
- [Icw] Rated Short-Time Withstand Current:
- 115 A 50°C - 1 s for power circuit || 105 A 50°C - 5 s for power circuit || 100 A 50°C - 10 s for power circuit || 75 A 50°C - 30 s for power circuit || 55 A 50°C - 1 min for power circuit || 50 A 50°C - 3 min for power circuit || 25 A 50°C - >= 15 m
- Net Weight:
- 0.225 kg
- Coil Technology:
- built-in bidirectional peak limiting diode suppressor
- Tightening Torque:
- 0.8-1.3 N.m screw clamp terminals Philips No 2 || 0.8-1.3 N.m screw clamp terminals flat Ø 6 mm || 0.8-1.3 N.m screw clamp terminals pozidriv No 2
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Ambient Air Temperature For Operation:
- -25-50°C
- Connections - Terminals:
- screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 mm²flexible with cable end || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 2 0.75-4
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC <= 400 Hz || Signaling circuit <= 690 V AC <= 400 Hz
- Maximum Operating Rate:
- 3600 cyc/h
- Toxic Heavy Metal Free:
- Yes
- [Uc] Control Circuit Voltage:
- 24 V DC
- Control Circuit Type:
- DC standard
- Overvoltage Category:
- III
- [Ith] Conventional Free Air Thermal Current:
- 20 A (at 60°C) for power circuit || 10 A (at 50°C) for Signaling circuit
- Irms Rated Making Capacity:
- 144 A AC for power circuit conforming to IEC 60947 || 110 A AC for Signaling circuit conforming to IEC 60947
- Inrush Power In W:
- 3-3 W 20°C)
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Mechanical Durability:
- 10 Mcycles