- Utilisation Category:
- AC-3 || AC-3e || AC-1 || AC-4
- Poles Description:
- 3P
- Operating Time:
- 30...40 ms coil energisation and NO closing || 10 ms coil de-energisation and NO opening
- Range:
- TeSys
- Electrical Durability:
- 1.3 Mcycles 12 A AC-3 <= 440 V || 1.3 Mcycles 12 A AC-3e <= 440 V || 0.3 Mcycles 20 A AC-1 <= 690 V || 0.02 Mcycles 72 A AC-4 <= 440 V
- Warranty:
- 18 months
- Environmental Disclosure:
- ENVPEP1503003EN
- Operating Altitude:
- 6561.68 ft (2000 m) without derating
- Mercury Free:
- Yes
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Standards:
- EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4
- Ambient Air Temperature For Operation:
- -25-50°C
- Mounting Support:
- plate || rail
- Device Short Name:
- LP1K
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV
- Pole Contact Composition:
- 3 NO
- [Icw] Rated Short-Time Withstand Current:
- 115 A 50°C - 1 s for power circuit || 105 A 50°C - 5 s for power circuit || 100 A 50°C - 10 s for power circuit || 75 A 50°C - 30 s for power circuit || 55 A 50°C - 1 min for power circuit || 50 A 50°C - 3 min for power circuit || 25 A 50°C - >= 15 m
- Weight:
- 0.225 kg
- Flame Retardance:
- V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Overvoltage Category:
- III
- [Uc] Control Circuit Voltage:
- 24 V DC
- Irms Rated Making Capacity:
- 144 A AC for power circuit conforming to IEC 60947 || 110 A AC for Signaling circuit conforming to IEC 60947
- Product Or Component Type:
- contactor
- Average Impedance:
- 3 mOhm - Ith 20 A 50 Hz for power circuit
- Reach Free Of Svhc:
- Yes
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Eu Rohs Directive:
- Compliant
- Circularity Profile:
- ENVEOLI1503003EN
- [Ie] Rated Operational Current:
- 12 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 12 A (at <60°C) at <= 440 V AC AC-3e for power circuit || 20 A (at <60°C) at <= 690 V AC AC-1 for power circuit
- Auxiliary Contact Composition:
- 1 NO
- Rohs Exemption Information:
- Yes
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- [Ith] Conventional Free Air Thermal Current:
- 20 A (at 60°C) for power circuit || 10 A (at 50°C) for Signaling circuit
- Contactor Application:
- resistive load || motor control
- Rated Breaking Capacity:
- 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conforming to IEC 60947
- Net Weight:
- 0.225 kg
- Control Circuit Voltage Limits:
- operational: 0.8...1.15 Uc (at <50°C) || drop-out: >= 0.10 Uc (at <50°C)
- Tightening Torque:
- 0.8-1.3 N.m screw clamp terminals Philips No 2 || 0.8-1.3 N.m screw clamp terminals flat Ø 6 mm || 0.8-1.3 N.m screw clamp terminals pozidriv No 2
- Ambient Air Temperature For Storage:
- -50-80°C
- Associated Fuse Rating:
- 25 A gG at <= 440 V for power circuit || 25 A aM for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947 || 10 A gG for Signaling circuit conforming to VDE 0660
- Permissible Ambient Air Temperature Around The Device:
- -40-70°C at Uc