- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Non Overlap Distance:
- 0.5 mm
- Weight:
- 0.48 kg
- Width:
- 90 mm
- Country of Origin:
- France
- Mounting Support:
- rail || plate
- Operating Time:
- 30...40 ms coil energisation and NO closing || 10 ms coil de-energisation and NO opening
- Control Circuit Voltage Limits:
- operational: 0.8...1.15 Uc (at <50°C) || drop-out: 0.1...0.75 Uc (at <50°C)
- Depth:
- 57 mm
- Net Weight:
- 0.48 kg
- Average Impedance:
- 3 mOhm - Ith 20 A 50 Hz for power circuit
- Control Circuit Type:
- DC standard
- Device Short Name:
- LP2K
- Overvoltage Category:
- III
- Warranty:
- 18 months
- Standards:
- EN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Pole Contact Composition:
- 3 NO
- Connections - Terminals:
- screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 mm²flexible with cable end || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 2 0.75-4
- Contactor Application:
- motor control || resistive load
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Circularity Profile:
- ENVEOLI1503003EN
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Ambient Air Temperature For Storage:
- -50-80°C
- Environmental Disclosure:
- ENVPEP1503003EN
- Auxiliary Contact Composition:
- 1 NC
- Auxiliary Contacts Type:
- instantaneous 1 NC
- Electrical Durability:
- 1.3 Mcycles 9 A AC-3 <= 440 V || 1.3 Mcycles 9 A AC-3e <= 440 V || 0.16 Mcycles 20 A AC-1 <= 690 V || 0.02 Mcycles 54 A AC-4 <= 440 V
- Reach Free Of Svhc:
- Yes
- Product Certifications:
- CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
- Product Name:
- TeSys K
- Flame Retardance:
- V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
- [Uc] Control Circuit Voltage:
- 48 V DC
- [Ue] Rated Operational Voltage:
- power circuit 690 V AC 50/60 Hz || Signaling circuit <= 690 V AC 50/60 Hz
- Sustainable Offer Status:
- Green Premium product
- Operating Altitude:
- 6561.68 ft (2000 m) without derating
- Mechanical Durability:
- 5 Mcycles
- Utilisation Category:
- AC-3 || AC-3e || AC-4 || AC-1
- Ambient Air Temperature For Operation:
- -25-50°C
- Product Or Component Type:
- reversing contactor
- [Ui] Rated Insulation Voltage:
- power circuit 600 V UL 508 || power circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-5-1 || Signaling circuit 600 V UL 508 || power circuit 600 V CSA C22.2 No 14 || Signaling circuit 600 V CSA
- Device Application:
- control
- Eu Rohs Directive:
- Compliant
- Associated Fuse Rating:
- 25 A gG at <= 440 V for power circuit || 25 A aM for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947 || 10 A gG for Signaling circuit conforming to VDE 0660
- Inrush Power In W:
- 3-3 W 20°C)
- Protective Treatment:
- TC IEC 60068 || TC DIN 50016