Schneider Electric

Schneider Electric LP4K090045BW3 Contactor, TeSys K, 4P, 4 NO, AC-1, lt or eq to 440V, 20A, 24VDC coil

(No reviews yet) Write a Review
SKU:
LP4K090045BW3
MPN:
LP4K090045BW3
Condition:
New
Flame Retardance:
V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
Rated Breaking Capacity:
110 A at 220...230 V conforming to IEC 60947 || 110 A at 380...400 V conforming to IEC 60947 || 110 A at 415 V conforming to IEC 60947 || 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conformin
Ambient Air Temperature For Storage:
-50-80°C
Heat Dissipation:
1.8-1.8 W
Mechanical Durability:
30 Mcycles
Product Or Component Type:
contactor
Control Circuit Type:
DC wide range
Average Impedance:
3 mOhm - Ith 20 A 50 Hz for power circuit
Overvoltage Category:
III
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Inrush Power In W:
1.8-1.8 W 20°C)
Control Circuit Voltage Limits:
operational: 0.7...1.3 Uc (at <50°C) || drop-out: >= 0.10 Uc (at <50°C)
Depth:
57 mm
Contactor Application:
resistive load
Sustainable Packaging:
Yes
Mercury Free:
Yes
Connections - Terminals:
solder pins 0.035 mm)
Utilisation Category:
AC-1
Poles Description:
4P
Ambient Air Temperature For Operation:
-25-50°C
Electrical Durability:
0.16 Mcycles 20 A AC-1 <= 690 V
Reach Free Of Svhc:
Yes
Net Weight:
0.235 kg
Eu Rohs Directive:
Compliant
Environmental Disclosure:
ENVPEP1503003EN
Irms Rated Making Capacity:
110 A AC for power circuit conforming to IEC 60947
Ip Degree Of Protection:
IP2X
[Icw] Rated Short-Time Withstand Current:
90 A 50°C - 1 s for power circuit || 85 A 50°C - 5 s for power circuit || 80 A 50°C - 10 s for power circuit || 60 A 50°C - 30 s for power circuit || 45 A 50°C - 1 min for power circuit || 40 A 50°C - 3 min for power circuit || 20 A 50°C - >= 15 min
Operating Altitude:
6561.68 ft (2000 m) without derating
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Pole Contact Composition:
4 NO
[Ui] Rated Insulation Voltage:
power circuit 600 V UL 508 || power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA C22.2 No 14
[Ie] Rated Operational Current:
20 A (at <60°C) at <= 690 V AC AC-1 for power circuit
Hold-In Power Consumption In W:
1.8-1.8 W 20°C
Maximum Operating Rate:
3600 cyc/h
Warranty:
18 months
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Range:
TeSys
Device Short Name:
LP4K
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC <= 400 Hz || Signaling circuit <= 690 V AC <= 400 Hz
Rohs Exemption Information:
Yes
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
[Uc] Control Circuit Voltage:
24 V DC
Associated Fuse Rating:
25 A gG at <= 440 V for power circuit || 25 A aM for power circuit
Coil Technology:
built-in bidirectional peak limiting diode suppressor