Schneider Electric

Schneider Electric LP5K1210BW3 Reversing contactor, TeSys K, 3P, AC-3, lt or eq to 440V 12 A, 1 NO, 24VDC coil

(No reviews yet) Write a Review
SKU:
LP5K1210BW3
MPN:
LP5K1210BW3
Condition:
New
Product Or Component Type:
reversing contactor
[Ie] Rated Operational Current:
20 A (at <50°C) at <= 440 V AC AC-1 for power circuit || 16 A (at <70°C) at 690 V AC AC-1 for power circuit || 12 A at <= 440 V AC AC-3 for power circuit || 12 A at <= 440 V AC AC-3e for power circuit
Poles Description:
3P
Contactor Application:
motor control || resistive load
Rated Breaking Capacity:
110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conforming to IEC 60947
Device Presentation:
preassembled with reversing power busbar
Minimum Switching Current:
5 mA for Signaling circuit
Device Application:
control
Motor Power Kw:
4 kW 480 V AC 50/60 Hz || 4 kW 500...600 V AC 50/60 Hz || 4 kW 660...690 V AC 50/60 Hz || 3 kW 220...230 V AC 50/60 Hz || 5.5 kW 380...415 V AC 50/60 Hz || 5.5 kW 440 V AC 50/60 Hz
Environmental Disclosure:
ENVPEP1503003EN
Flame Retardance:
V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
Product Name:
TeSys K
Mechanical Robustness:
shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27 || vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6 || vibrations contactor opened2 Gn, 5...300 Hz IEC 60068
Ambient Air Temperature For Operation:
-25-50°C
Warranty:
18 months
Control Circuit Voltage Limits:
operational: 0.7...1.30 Uc (at <50°C) || drop-out: 0.1...0.7 Uc (at <50°C)
Coil Technology:
built-in bidirectional peak limiting diode suppressor
Protective Treatment:
TC IEC 60068 || TC DIN 50016
Product Certifications:
CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
Ambient Air Temperature For Storage:
-50-80°C
Connections - Terminals:
screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 mm²flexible with cable end || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 2 0.75-4
[Ui] Rated Insulation Voltage:
power circuit 600 V UL 508 || power circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-5-1 || Signaling circuit 600 V UL 508 || power circuit 600 V CSA C22.2 No 14 || Signaling circuit 600 V CSA
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
[Ue] Rated Operational Voltage:
power circuit 690 V AC 50/60 Hz || Signaling circuit <= 690 V AC 50/60 Hz
Net Weight:
0.49 kg
Reach Free Of Svhc:
Yes
Associated Fuse Rating:
25 A gG at <= 440 V for power circuit || 25 A aM for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947 || 10 A gG for Signaling circuit conforming to VDE 0660
Country of Origin:
France
Hold-In Power Consumption In W:
1.8-1.8 W 20°C
Sustainable Offer Status:
Green Premium product
Operating Time:
10...20 ms coil de-energisation and NO opening || 30...40 ms coil energisation and NO closing
Mounting Support:
plate || rail
Pole Contact Composition:
3 NO
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Average Impedance:
3 mOhm - Ith 20 A 50 Hz for power circuit
Auxiliary Contacts Type:
instantaneous 1 NO
Weight:
0.49 kg
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Maximum Operating Rate:
3600 cyc/h
Utilisation Category:
AC-4 || AC-1 || AC-3 || AC-3e
Insulation Resistance:
> 10 MOhm for Signaling circuit
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Heat Dissipation:
1.8-1.8 W
[Icw] Rated Short-Time Withstand Current:
115 A 50°C - 1 s for power circuit || 105 A 50°C - 5 s for power circuit || 100 A 50°C - 10 s for power circuit || 75 A 50°C - 30 s for power circuit || 55 A 50°C - 1 min for power circuit || 50 A 50°C - 3 min for power circuit || 80 A - 1 s for Sign
Overvoltage Category:
III
$274.00

Description

TeSys K reversing contactor, 3 poles (3NO), for motor control applications up to 12A/690V AC-3 (5.5kW@400V). It provides low consumption 24V DC coils with transient suppressor module, 2NO built-in auxiliary contacts, connection by screw clamp terminals. For operating rates until 600 cycles/hour in AC-3 and environments until 50°C, it procures reliability and durability to standard applications. Compact (90mm width), DIN-rail mounting or screw fixing. With pre-wired reversing power connections, mechanical interlock (without electrical interlocking). Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
View AllClose