- Connections - Terminals:
- screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 2 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2
- Fire Resistance:
- 850°C IEC 60695-2-1
- Mounting Support:
- under contactor || plate, with specific accessories || rail, with specific accessories
- Range:
- TeSys
- Product Certifications:
- UL || CSA || UKCA
- Power Dissipation Per Pole:
- 2 W
- Thermal Overload Class:
- class 10A IEC 60947-4-1
- Circularity Profile:
- ENVEOLI2211018
- Eu Rohs Directive:
- Compliant with Exemptions
- Mechanical Robustness:
- shocks NO contact10 Gn for 11 ms IEC 60068-2-27 || shocks NC contact10 Gn for 11 ms IEC 60068-2-27 || vibrations NO contact2 Gn, 5...300 Hz IEC 60068-2-6 || vibrations NC contact2 Gn, 5...300 Hz IEC 60068-2-6
- Warranty:
- 18 months
- Country of Origin:
- France
- Product Compatibility:
- LC7K || LP1K || LP4K || LC1K
- Tightening Torque:
- 1.3 N.m screw clamp terminals Philips No 2 || 1.3 N.m screw clamp terminals flat Ø 6 mm || 1.3 N.m screw clamp terminals pozidriv No 2
- Weight:
- 0.145 kg
- Associated Fuse Rating:
- 6 A gG for Signaling circuit conforming to VDE 0660 || 6 A gG for Signaling circuit conforming to IEC 60947
- [Ith] Conventional Free Air Thermal Current:
- 6 A Signaling circuit
- Ip Degree Of Protection:
- IP2X conforming to IEC 60529
- Standards:
- IEC 60947 || VDE 0660 || BS 4941 || NF C 63-650
- Protective Treatment:
- TC IEC 60068 || TC DIN 50016
- Phase Failure Sensitivity:
- yes IEC 60947-4-1
- Network Type:
- DC || AC
- Thermal Protection Adjustment Range:
- 3.7-5.5 A
- Control Type:
- Red push-button trip test function || Blue push-button stop and manual reset || selector switch manual or automatic reset
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Device Short Name:
- LR2K
- Product Name:
- TeSys LRK
- Sustainable Offer Status:
- Green Premium product
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- [Ue] Rated Operational Voltage:
- <= 690 V power circuit || 690 V AC AC-15 Signaling circuit || 250 V DC DC-13 Signaling circuit
- Flame Retardance:
- V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
- Rohs Exemption Information:
- Yes
- Net Weight:
- 0.145 kg
- Relay Application:
- motor protection
- Depth:
- 65 mm
- Network Frequency:
- <= 400 Hz
- [Ui] Rated Insulation Voltage:
- power circuit 690 V BS 4941 || power circuit 690 V IEC 60947 || power circuit 750 V VDE 0110 group C || power circuit 600 V CSA C22.2 No 14
- Operating Altitude:
- 6561.68 ft (2000 m) without derating
- Ambient Air Temperature For Operation:
- -20-55°C without derating IEC 60947 || -30-60°C with derating IEC 60947
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV
- Ambient Air Temperature For Storage:
- -40-70°C
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Mercury Free:
- Yes
- Product Or Component Type:
- differential thermal overload relay
- Auxiliary Contact Composition:
- 1 NO + 1 NC