Schneider Electric LR9D02 Overload relay, TeSys LRD, motor protection, 0.4A to 2A, 3 phase, withstand 6kV impulse, 2kV surge, electronic thermal
Schneider Electric
$64.41
TeSys LR9D electronic overload relay, 2A/690V, thermal setting range 0.4-2A, selectable tripping class 5-10-20-30, for protection of 3-phase motors 0.12-0.75kW@400V. Differential device with phase failure and load unbalance detection. It provides a thermal adjustement dial, buttons for test, stop and reset as well as manual-automatic reset selector, dipswitches for tripping class selection, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. With a large thermal setting range 0.4-2A, a selectable tripping class 5-10-20-30 and phase unbalance detection, it protects motors 0.18 to 0.75kW@400V. Connection by screw clamp terminals, it connects directly to the bottom terminals of 3-pole contactors LC1D09-D38. Mounting on DIN rail or screw fixing, separated from contactor, with use of the terminal block LAD7B205 (to be ordered separately). Multi-standards certified (IEC, UL, CSA, CCC), Green Premium compliant (RoHs/Reach).
- Ambient Air Temperature For Operation:
- -25-70°C IEC 60255-8
- Associated Fuse Rating:
- 5 A gG for Signaling circuit || 5 A BS for Signaling circuit
- Circularity Profile:
- ENVEOLI1502001EN
- Dielectric Strength:
- 6 kV 50 Hz IEC 60255-5
- Mercury Free:
- Yes
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV
- [Ui] Rated Insulation Voltage:
- power circuit 1000 V || Signaling circuit 690 V
- Weight:
- 0.18 kg
- Product Certifications:
- IECEE CB Scheme || UL || CSA || CCC
- Range:
- TeSys
- Thermal Protection Adjustment Range:
- 0.4-2 A
- [Ue] Rated Operational Voltage:
- 690 V power circuit || 660 V Signaling circuit
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Environmental Disclosure:
- ENVPEP1502001EN
- Country of Origin:
- China
- Net Weight:
- 0.18 kg
- Time Range:
- 1.5...4 min - automatic reset time
- Electromagnetic Compatibility:
- surge withstand 2 kV common mode IEC 61000-4-5 || resistance to electrostatic discharge 8 kV IEC 61000-4-2 || immunity to radiated radio-electrical interference 10 V/m IEC 61000-4-3 || immunity to fast transients 2 kV IEC 61000-4-4
- Standards:
- EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4 || GB/T 14048.5
- Product Or Component Type:
- electronic thermal overload relay
- Control Type:
- Red push-button stop and manual reset || White 2 microswitches adjustable trip class || Red knob automatic reset || White dial full-load current adjustment
- Product Compatibility:
- LC1D25 || LC1D09 || LC1D32 || LC1D38 || LC1D18 || LC1D12
- [Ith] Conventional Free Air Thermal Current:
- 5 A Signaling circuit
- Tightening Torque:
- control circuit 0.8 N.m screw clamp terminals || power circuit 3.1 N.m screw clamp terminals
- Device Short Name:
- LR9D
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Phase Failure Sensitivity:
- phase difference > 40% 3-3 s IEC 60947-4-1
- Thermal Overload Class:
- class 5…30
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Product Name:
- TeSys LRD
- Mechanical Robustness:
- vibrations 10...150 Hz6 Gn IEC 60068-2-6 || shocks 11 ms15 gn IEC 60068-2-7
- California Proposition 65:
- WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
- Tripping Threshold:
- 1.25 In IEC 60947-4-1
- Sustainable Offer Status:
- Green Premium product
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Eu Rohs Directive:
- Compliant with Exemptions
- Depth:
- 79.9 mm
- Power Consumption In W:
- 300 mW
- Rohs Exemption Information:
- Yes
- Operating Altitude:
- 6561.68 ft (2000 m) without derating
- Ambient Air Temperature For Storage:
- -55-80°C
- Mounting Support:
- under contactor || plate, with specific accessories || rail, with specific accessories
- Relay Application:
- motor protection
- Connections - Terminals:
- control circuit screw clamp terminals 1 2.5-2.5 mm² solid or flexible - without cable end || power circuit screw clamp terminals 1 16-16 mm² solid or flexible - without cable end