- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Eu Rohs Directive:
- Compliant with Exemptions
- Depth:
- 125 mm
- Ambient Air Temperature For Storage:
- -60-70°C
- Thermal Protection Adjustment Range:
- 90-150 A
- Net Weight:
- 0.885 kg
- Circularity Profile:
- ENVEOLI2212018
- Network Frequency:
- 50-60 Hz
- Dielectric Strength:
- 1.89 kV 50 Hz IEC 60947-1
- Tripping Threshold:
- 1.05 +/- 0.06 In alarm IEC 60947-4-1 || 1.12 +/- 0.06 In de-energisation IEC 60947-4-1
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Ambient Air Temperature For Operation:
- -20-60°C without derating IEC 60947-4-1
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947-1
- Device Short Name:
- LR9D
- Switching Capacity In Ma:
- 0...150 mA
- Operating Altitude:
- <= 6561.68 ft (2000 m) without derating
- Product Certifications:
- UL || CSA || CCC || UKCA
- Pvc Free:
- Yes
- Thermal Overload Class:
- class 10 IEC 60947-4-1
- Climatic Withstand:
- IACS E10
- Mounting Support:
- under contactor || rail
- Range:
- TeSys
- Relay Application:
- motor protection
- Maximum Voltage Drop:
- <2.5 V closed state
- Connections - Terminals:
- power circuit bars || control circuit screw clamp terminals 1 0.5-1.5 mm² flexible without cable end || control circuit screw clamp terminals 2 0.5-1.5 mm² flexible without cable end || alarm circuit screw clamp terminals 1 0.5-1.5 mm² flexible wi
- Mechanical Robustness:
- vibrations2 Gn, 5...300 Hz IEC 60068-2-6 || shocks13 Gn for 11 ms IEC 60068-2-7
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Environmental Disclosure:
- ENVPEP2212018
- Product Compatibility:
- NSX circuit breaker || LC1D150 || LC1D115
- [Ue] Rated Operational Voltage:
- 690 V AC 0...400 Hz power circuit IEC 60947-4-1
- Temperature Compensation:
- -20-60°C
- Supply Voltage Limits:
- 17-32 V
- Warranty:
- 18 months
- Ip Degree Of Protection:
- IP20 conforming to IEC 60529
- [Ith] Conventional Free Air Thermal Current:
- 5 A Signaling circuit
- Country of Origin:
- United States
- Network Type:
- AC
- Standards:
- EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4 || GB/T 14048.5
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Signaling Function:
- alarm
- Mercury Free:
- Yes
- [Us] Rated Supply Voltage:
- 24 V DC
- Weight:
- 0.885 kg
- Tightening Torque:
- alarm circuit 0.45 N.m screw clamp terminals || power circuit 18 N.m bars M8 || control circuit 1.2 N.m screw clamp terminals
- Rohs Exemption Information:
- Yes