- Tripping Threshold:
- 1.05 +/- 0.06 In alarm IEC 60947-4-1 || 1.12 +/- 0.06 In de-energisation IEC 60947-4-1
- Mechanical Robustness:
- vibrations2 Gn, 5...300 Hz IEC 60068-2-6 || shocks13 Gn for 11 ms IEC 60068-2-7
- Ambient Air Temperature For Storage:
- -60-70°C
- Ip Degree Of Protection:
- IP20 conforming to IEC 60529
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Mounting Support:
- under contactor || rail
- Operating Altitude:
- <= 6561.68 ft (2000 m) without derating
- Ambient Air Temperature For Operation:
- -20-60°C without derating IEC 60947-4-1
- Mercury Free:
- Yes
- Depth:
- 125 mm
- Relay Application:
- motor protection
- Network Type:
- AC
- Climatic Withstand:
- IACS E10
- Associated Fuse Rating:
- 4 A gG for Signaling circuit || 4 A BS for Signaling circuit
- Range:
- TeSys
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Product Name:
- TeSys LRD || TeSys Deca
- Network Frequency:
- 50-60 Hz
- Net Weight:
- 0.9 kg
- Product Or Component Type:
- electronic thermal overload relay
- Rohs Exemption Information:
- Yes
- Standards:
- EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4 || GB/T 14048.5
- Dielectric Strength:
- 1.89 kV 50 Hz IEC 60947-1
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Pvc Free:
- Yes
- Device Short Name:
- LR9D
- Country of Origin:
- France
- [Ue] Rated Operational Voltage:
- 690 V AC 0...400 Hz power circuit IEC 60947-4-1
- Thermal Protection Adjustment Range:
- 90-150 A
- Eu Rohs Directive:
- Compliant with Exemptions
- Supply Voltage Limits:
- 17-32 V
- Control Type:
- Red push-button stop || Blue push-button reset
- Temperature Compensation:
- -20-60°C
- Thermal Overload Class:
- class 10/20 IEC 60947-4-1
- [Ui] Rated Insulation Voltage:
- power circuit 1000 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL
- Product Compatibility:
- NSX circuit breaker || LC1D115 || LC1D150
- [Us] Rated Supply Voltage:
- 24 V DC
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947-1
- Product Certifications:
- UL || CSA || CCC
- Weight:
- 0.9 kg
- [Ith] Conventional Free Air Thermal Current:
- 5 A Signaling circuit
- Maximum Voltage Drop:
- <2.5 V closed state
- Environmental Disclosure:
- ENVPEP2212018
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Switching Capacity In Ma:
- 0...150 mA