Schneider Electric LRA36250U31X Circuit breaker, PowerPacT L, 250A, 3 pole, 600VAC, 100kA, I-Line, MicroLogic 3.3, 80%, ABC
Schneider Electric
$11,745.00
PowerPacT L-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT L-Frame circuit breakers are available with electronic trip units. All PowerPacT L-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT L circuit breakers are available in 3 and 4-pole unit mount, I-Line, and drawout constructions. This PowerPacT L, 250A, 3 pole, circuit breaker has an interrupting rating of 100kA at 600VAC. This circuit breaker provides MicroLogic Standard with a 3.3 trip unit and an LI function. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Mounting Mode:
- I-Line bracket)
- Ambient Air Temperature For Operation:
- -25-70°C
- Trip Unit Name:
- MicroLogic 3.3
- Pollution Degree:
- 3 IEC 60947-1
- Rohs Exemption Information:
- Yes
- Mercury Free:
- Yes
- Utilisation Category:
- category A
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Product Name:
- PowerPact L
- Length:
- 31 mm
- Height:
- 6 in
- Circuit Breaker Application:
- HACR rated
- Color:
- Black
- Height:
- 340 mm
- Product Or Component Type:
- circuit breaker
- Tightening Torque:
- 50-50 N.m 35-300 mm² (AWG 2...600 kcmil) || 50-50 N.m 35-240 mm² (AWG 2...500 kcmil)
- Ambient Air Temperature For Storage:
- -50-85°C
- Sustainable Offer Status:
- Green Premium product
- Mounting Support:
- bracket
- Weight:
- 6.2 kg
- Control Type:
- toggle
- Breaking Capacity Code:
- R
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Line Rated Current:
- 250-250 A
- Environmental Disclosure:
- ENVPEP1406010EN
- Eu Rohs Directive:
- Compliant
- Local Signaling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Net Weight:
- 6.2 kg
- Range:
- PowerPact
- Product Certifications:
- UL || CSA || NOM
- Poles Description:
- 3P
- Phase Connection:
- ABC
- Device Application:
- distribution
- Terminal Identifier:
- AL400L61K3
- Suitability For Isolation:
- yes IEC 60947-2
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.3, LI
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Device Short Name:
- L-Frame
- Protection Technology:
- current limiter
- Country of Origin:
- United States
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Mounting Height:
- 6 in
- Warranty:
- 18 months
- [Ics] Rated Service Breaking Capacity:
- 150 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 125 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 75 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 690 V AC 50/60 Hz IEC 60947-2
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Electrical Connection:
- I-Line connection, line || lugs, load