Schneider Electric

Schneider Electric LRD02 TeSys Deca thermal overload relays - 0.16...0.25 A - class 10A

(No reviews yet) Write a Review
SKU:
LRD02
MPN:
LRD02
Condition:
New
Phase Failure Sensitivity:
tripping current 130 % of Ir on two phase, the last one at 0
Thermal Protection Adjustment Range:
0.16-0.25 A
Tripping Threshold:
1.14 +/- 0.06 Ir IEC 60947-4-1
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Toxic Heavy Metal Free:
Yes
Ambient Air Temperature For Operation:
-20-60°C without derating IEC 60947-4-1
Circularity Profile:
ENVEOLI0802006
Temperature Compensation:
-20-60°C
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals || power circuit 1.7 N.m screw clamp terminals
Range:
TeSys || TeSys Deca
Mercury Free:
Yes
Warranty:
18 months
Weight:
0.124 kg
Dielectric Strength:
1.89 kV 50 Hz IEC 60947-1
Mounting Support:
plate, with specific accessories || rail, with specific accessories || under contactor
Country of Origin:
Mexico
Network Type:
DC || AC
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Product Certifications:
IEC || UL || CSA || CCC || EAC || BV || RINA || DNV-GL || LROS (Lloyds register of shipping) || ATEX INERIS || UKCA
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || power circuit 690 V IEC 60947-4-1
Product Name:
TeSys LRD || TeSys Deca
Associated Fuse Rating:
4 A gG for Signaling circuit || 4 A BS for Signaling circuit
Product Or Component Type:
differential thermal overload relay
Device Short Name:
LRD
Eu Rohs Directive:
Compliant
Rohs Exemption Information:
Yes
[Ue] Rated Operational Voltage:
690 V AC 0...400 Hz power circuit IEC 60947-4-1
Thermal Overload Class:
class 10A IEC 60947-4-1
Network Frequency:
0...400 Hz
Depth:
70 mm
Climatic Withstand:
IACS E10
Environmental Disclosure:
ENVPEP080206EN
Product Compatibility:
LC1D25 || LC1D38 || LC1D12 || LC1D09 || LC1D18 || LC1D32
Sustainable Offer Status:
Green Premium product
Flame Retardance:
V1 conforming to UL 94
Ambient Air Temperature For Storage:
-60-70°C
Mechanical Robustness:
vibrations6 Gn IEC 60068-2-6 || shocks15 Gn for 11 ms IEC 60068-2-7
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4 || GB/T 14048.5 || EN 50495
Relay Application:
motor protection
Control Type:
Red push-button stop || Blue push-button reset
Net Weight:
0.124 kg
[Uimp] Rated Impulse Withstand Voltage:
6 kV
Permissible Current:
3 A 120 V AC-15 Signaling circuit || 0.22 A 125 V DC-13 Signaling circuit
Ip Degree Of Protection:
IP20 conforming to IEC 60529
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
$60.00

Description

LRD02 is a TeSys LRD thermal overload relay from Schneider Electric to be used with a TeSys D contactor. It protects motors 0.06kW@400V thanks to a thermal range 0.16-0.25A, a tripping class 10A and phase unbalance protection. LRD02 is a TeSys LRD thermal overload relay from Schneider Electric for direct mounting on TeSys D contactors. With a thermal setting range 0.16-0.25A, a tripping class 10A and phase unbalance detection, it protects motors 0.06kW@400V. It provides manual test & reset buttons, automatic reset, trip auxiliary contact and flag indicator. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Thermal overload protection relay, bimetallic type, with phase unbalance protection (differential). Direct mounting on the bottom terminals of a Tesys contactor LC1D09-D38 to form a compact starter. Light and compact, 45mm wide. Temperature compensated for a good accuracy of the protection. Manual control with test & reset buttons, manual / automatic reset selector. Trip signaling with 1NO+1NC auxiliary contacts and trip flag indicator. Can be completed with terminal blocks for separate mounting (LAD7B, LAD96) and remote control devices (LAD703, LA7D03).