- Ip Degree Of Protection:
- IP20 conforming to IEC 60529
- Relay Application:
- motor protection
- Permissible Current:
- 3 A 120 V AC-15 Signaling circuit || 0.22 A 125 V DC-13 Signaling circuit
- Depth:
- 76 mm
- Warranty:
- 18 months
- Mercury Free:
- Yes
- Range:
- TeSys || TeSys Deca
- Tripping Threshold:
- 1.14 +/- 0.06 Ir IEC 60947-4-1
- [Ue] Rated Operational Voltage:
- 690 V AC 0...400 Hz power circuit IEC 60947-4-1
- Net Weight:
- 0.144 kg
- Mounting Support:
- plate, with specific accessories || rail, with specific accessories || under contactor
- Sustainable Packaging:
- Yes
- Device Short Name:
- LRD
- Environmental Disclosure:
- ENVPEP080206EN
- Temperature Compensation:
- -20-60°C
- Thermal Protection Adjustment Range:
- 0.4-0.63 A
- [Ui] Rated Insulation Voltage:
- power circuit 600 V CSA || power circuit 600 V UL || power circuit 690 V IEC 60947-4-1
- Sustainable Offer Status:
- Green Premium product
- Phase Failure Sensitivity:
- tripping current 130 % of Ir on two phase, the last one at 0
- Mechanical Robustness:
- shocks15 Gn for 11 ms IEC 60068-2-7 || vibrations3 GN IEC 60068-2-6
- Circularity Profile:
- ENVEOLI0802006
- California Proposition 65:
- WARNING: Cancer - www.P65Warnings.ca.gov
- Tightening Torque:
- control circuit 1.7 N.m screw clamp terminals || power circuit 2.3 N.m lugs-ring terminals M4
- Climatic Withstand:
- IACS E10
- Associated Fuse Rating:
- 4 A gG for Signaling circuit || 4 A BS for Signaling circuit
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Product Certifications:
- IEC || UL || CSA || EAC || ABS || ATEX INERIS || UKCA
- Thermal Overload Class:
- class 20 IEC 60947-4-1
- Rohs Exemption Information:
- Yes
- Product Name:
- TeSys LRD || TeSys Deca
- Weight:
- 0.144 kg
- Country of Origin:
- Singapore
- Network Frequency:
- 0...400 Hz
- Standards:
- EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || EN 50495
- Ambient Air Temperature For Operation:
- -20-60°C without derating IEC 60947-4-1
- Network Type:
- DC || AC
- [Ith] Conventional Free Air Thermal Current:
- 5 A Signaling circuit
- Dielectric Strength:
- 1.89 kV 50 Hz IEC 60947-1
- Eu Rohs Directive:
- Compliant
- Ambient Air Temperature For Storage:
- -60-70°C
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Toxic Heavy Metal Free:
- Yes
- Product Or Component Type:
- differential thermal overload relay
- Product Compatibility:
- LC1D32 || LC1D18 || LC1D09 || LC1D12 || LC1D38 || LC1D25
- China Rohs Regulation: