Schneider Electric

Schneider Electric LRD06L6 Thermal overload relay,TeSys Deca,1-1.6A,1NO+1NC,class 20,lugs ring terminal

(No reviews yet) Write a Review
SKU:
LRD06L6
MPN:
LRD06L6
Condition:
New
California Proposition 65:
WARNING: Cancer - www.P65Warnings.ca.gov
Associated Fuse Rating:
4 A gG for Signaling circuit || 4 A BS for Signaling circuit
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || power circuit 690 V IEC 60947-4-1
[Ith] Conventional Free Air Thermal Current:
5 A Signaling circuit
Auxiliary Contact Composition:
1 NO + 1 NC
Permissible Current:
3 A 120 V AC-15 Signaling circuit || 0.22 A 125 V DC-13 Signaling circuit
Toxic Heavy Metal Free:
Yes
Connections - Terminals:
control circuit screw clamp terminals 2 1-2.5 mm² flexible without cable end || control circuit screw clamp terminals 2 1-2.5 mm² flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm² solid without cable end || power circuit
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Network Type:
AC || DC
[Uimp] Rated Impulse Withstand Voltage:
6 kV
Network Frequency:
0...400 Hz
Phase Failure Sensitivity:
tripping current 130 % of Ir on two phase, the last one at 0
Warranty:
18 months
Thermal Overload Class:
class 20 IEC 60947-4-1
Ambient Air Temperature For Operation:
-20-60°C without derating IEC 60947-4-1
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Mounting Support:
plate, with specific accessories || rail, with specific accessories || under contactor
Product Or Component Type:
differential thermal overload relay
Country of Origin:
Thailand
Temperature Compensation:
-20-60°C
Device Short Name:
LRD
Climatic Withstand:
IACS E10
Environmental Disclosure:
ENVPEP080206EN
Circularity Profile:
ENVEOLI0802006
Mechanical Robustness:
shocks15 Gn for 11 ms IEC 60068-2-7 || vibrations3 GN IEC 60068-2-6
Mercury Free:
Yes
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals || power circuit 2.3 N.m lugs-ring terminals M4
[Ue] Rated Operational Voltage:
690 V AC 0...400 Hz power circuit IEC 60947-4-1
Product Certifications:
IEC || UL || CSA || EAC || ABS || ATEX INERIS || UKCA
Control Type:
Red push-button stop || Blue push-button reset
Dielectric Strength:
1.89 kV 50 Hz IEC 60947-1
Ip Degree Of Protection:
IP20 conforming to IEC 60529
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || EN 50495
Product Compatibility:
LC1D38 || LC1D12 || LC1D25 || LC1D32 || LC1D18 || LC1D09
Ambient Air Temperature For Storage:
-60-70°C
Product Name:
TeSys LRD || TeSys Deca
Net Weight:
0.144 kg
Weight:
0.144 kg
Relay Application:
motor protection
Eu Rohs Directive:
Compliant
Depth:
76 mm
Tripping Threshold:
1.14 +/- 0.06 Ir IEC 60947-4-1
Sustainable Offer Status:
Green Premium product
Rohs Exemption Information:
Yes
$60.00