Mechanical Robustness:
vibrations6 Gn IEC 60068-2-6 || shocks15 Gn for 11 ms IEC 60068-2-7
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Rohs Exemption Information:
Yes
Product Name:
TeSys LRD || TeSys Deca
Network Frequency:
0...400 Hz
Permissible Current:
0.72 A 500 V AC-15 Signaling circuit || 0.06 A 440 V DC-13 Signaling circuit
Product Certifications:
IEC || UL || CSA || CCC || EAC || ATEX INERIS || UKCA
Mercury Free:
Yes
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4 || GB/T 14048.5 || EN 50495
Device Short Name:
LRD
Country of Origin:
United States
Weight:
0.51 kg
[Ith] Conventional Free Air Thermal Current:
5 A Signaling circuit
Temperature Compensation:
-20-60°C
Flame Retardance:
V1 conforming to UL 94
Thermal Protection Adjustment Range:
63-80 A
Ambient Air Temperature For Operation:
-20-60°C without derating IEC 60947-4-1
[Ui] Rated Insulation Voltage:
power circuit 1000 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947-1
Ip Degree Of Protection:
IP20 conforming to IEC 60529
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Eu Rohs Directive:
Compliant
Network Type:
DC || AC
Auxiliary Contact Composition:
1 NO + 1 NC
Connections - Terminals:
power circuit screw clamp terminals 1 4-35 mm² flexible without cable end || power circuit screw clamp terminals 1 4-35 mm² flexible with cable end || power circuit screw clamp terminals 1 4-35 mm² solid without cable end || control circuit screw
Warranty:
18 months
Dielectric Strength:
2.2 kV 50 Hz IEC 60947-1
Phase Failure Sensitivity:
tripping current 130 % of Ir on two phase, the last one at 0
Climatic Withstand:
IACS E10
[Ue] Rated Operational Voltage:
1000 V AC 0...400 Hz power circuit IEC 60947-4-1
Range:
TeSys
Thermal Overload Class:
class 10A IEC 60947-4-1
Mounting Support:
plate, with specific accessories || rail, with specific accessories || under contactor
Reach Free Of Svhc:
Yes
Control Type:
Red push-button stop || Blue push-button reset
Sustainable Offer Status:
Green Premium product
Environmental Disclosure:
ENVPEP110101EN
Product Compatibility:
LC1D80 || LC1D95
Ambient Air Temperature For Storage:
-60-70°C
Tripping Threshold:
1.14 +/- 0.06 Ir IEC 60947-4-1
Toxic Heavy Metal Free:
Yes
Net Weight:
0.51 kg
Product Or Component Type:
differential thermal overload relay
Circularity Profile:
ENVEOLI1101001
Depth:
115 mm
$127.00

Description

TeSys LRD overload relays are designed to be used with TeSys D contactors to make a motor starter. This overload relay can be used with 80 amp through 95 amp TeSys D contactors. These differential thermal overload relays detect over currents in the lines to the motor. When an overcurrent is detected the overload relay working with the contactor will disconnect the power to the motor. This will minimize the damage to the motor windings. This overload relay has an adjustable trip current rating of 63 to 80 amperes. This trip current rating is calibrated per Class 10A. Multi standards certified (IEC, UL, CSA, CCC, EAC, ATEX, Marine), Green Premium compliant (RoHs/Reach).