Schneider Electric

Schneider Electric LTMR08DBD Motor controller, TeSys T, Motor Management, DeviceNet, 6 logic inputs, 3 relay logic outputs, 0.4 to 8A, 24VDC

(No reviews yet) Write a Review
SKU:
LTMR08DBD
MPN:
LTMR08DBD
Condition:
New
Warranty:
18 months
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Depth:
122.5 mm
Web Services:
web server
Fire Resistance:
650°C EN/IEC 60695-2-12 || 960°C UL 94
Network And Machine Diagnosis Type:
fault recording || waiting time after overload tripping || remaining operating time before overload tripping || phase fault and earth fault trip counters || starting current and time || trip history information || trip context information || motor co
Protective Treatment:
12 x 24 hour cycles EN/IEC 60068-2-30 || 48 h EN/IEC 60070-2-11 || TH EN/IEC 60068
Rohs Exemption Information:
Yes
Standards:
EN 60947-4-1 || CSA C22.2 No 14 || UL 508 || IACS E10 || IEC 60947-4-1
Connections - Terminals:
control circuit connector 1 0.25-2.5 mm² AWG 24...AWG 14)flexible with cable end || control circuit connector 1 0.2-2.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 1 0.25-2.5 mm² AWG 24...AWG 14)flexible without cab
Maximum Operating Frequency:
2 Hz
Operating Altitude:
<= 6561.68 ft (2000 m) without derating
Electromagnetic Compatibility:
electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || control circuit: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 || communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 || relay ou
[Uimp] Rated Impulse Withstand Voltage:
6 kV current or voltage measurement circuit EN/IEC 60947-4-1 || 0.8 kV communication circuit EN/IEC 60947-4-1 || 0.8 kV supply, inputs and outputs EN/IEC 60947-4-1
Sustainable Offer Status:
Green Premium product
Short-Circuit Withstand:
100 kA conforming to EN/IEC 60947-4-1
Mercury Free:
Yes
Protection Type:
thermal overload protection || overload || power factor variation || reverse polarity protection || earth-leakage protection || thermal protection || overload (long time) || phase failure || load fluctuation || phase unbalance || locked rotor
Pollution Degree:
3
Ambient Air Temperature For Operation:
-20-60°C
Ambient Air Temperature For Storage:
-40-80°C
[Us] Rated Supply Voltage:
24 V DC
Device Short Name:
LTMR
Range:
TeSys
Measurement Accuracy:
5...15 % earth fault current internal measurement || 1 % voltage 100...830 V) || 3 % power factor || 5 % earth fault current external measurement || +/- 30 min/year internal clock || 0,02 Temperature || 1 % current || 5 % active and reactive power
Associated Fuse Rating:
4 A gG output || 0.5 A gG control circuit
Compatibility Code:
LTMR
Ip Degree Of Protection:
IP20
Mechanical Robustness:
vibrations mounted on symmetrical rail1 Gn, 5...300 Hz EN/IEC 60068-2-6 || vibrations plate mounted4 Gn, 5...300 Hz EN/IEC 60068-2-6 || shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27
Circularity Profile:
ENVEOLI100411EN_V2
Eu Rohs Directive:
Compliant with Exemptions
Current Consumption:
56...127 mA
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Net Weight:
0.53 kg
Overvoltage Category:
III
Contacts Type And Composition:
1 NO + 1 NC fault signal || 3 NO
Weight:
0.53 kg
Current State 1 Guaranteed:
logic input < 15 V 2...15 mA 15 ms
Maximum Operating Rate:
1800 cyc/h
Tightening Torque:
control circuit 0.5-0.6 N.m flat 3 mm
Product Or Component Type:
motor controller
Country of Origin:
China
Bus Type:
DeviceNet ISO 1198 1...64 125...500 kbit/s, terminal block 4 twisted shielded pairs cable
Pvc Free:
Yes
Product Name:
TeSys T
Device Application:
equipment monitoring and control
Metering Type:
phase current I1, I2, I3 RMS || temperature || earth-fault current || average current Iavg || imbalance current
Environmental Disclosure:
ENVPEP060308EN_V2
$750.00

Description

TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. TeSys T manages most critical processes while reducing downtime and increasing productivity. TeSys T is a flexible system that integrates seamlessly into your automation system through five major communication protocols. TeSys T predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range. This controller is the central component in the motor management system. The module manages the basic functions of the motor management system. It manages the measurement of 3 phase current via integral current transformers from 0.4 to 100 A or up to 810 A by external current transformers. It also measures ground current with internal or external ground sensors, motor temperature and the inputs and outputs for the various motor control modes, detected fault management and other functions. DeviceNet protocol is used by this controller. This module has 6 discrete logic inputs, 3 relay logic outputs and a relay output for detected fault signaling overload relay. The current range of this controller is 0.4 to 8 amperes. 24 VDC is used to power this controller. Controller is 2.40 inches tall, 3.58 inches wide and 4.82 inches deep. Controller weighs 1.17 lbs. Controller has the following certifications: UL, CSA NOM, ATEX, BV, EAC, RINA, LROS, DNV, ABS, GL, KERI, RMRoS, C-Tick and CCC.
View AllClose