Schneider Electric

Schneider Electric LTMR100EBD Motor controller, TeSys T, Motor Management, Ethernet/IP, Modbus/TCP, 6 logic inputs, 3 logic outputs, 5 to 100A, 24VDC

(No reviews yet) Write a Review
SKU:
LTMR100EBD
MPN:
LTMR100EBD
Condition:
New
Standards:
IEC 60947-4-1 || UL 508 || IACS E10 || EN 60947-4-1 || CSA C22.2 No 14
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Halogen Content Performance:
Halogen free plastic parts product
Depth:
122.5 mm
Short-Circuit Withstand:
100 kA conforming to EN/IEC 60947-4-1
Contacts Type And Composition:
1 NO + 1 NC fault signal || 3 NO
Web Services:
web server
Bus Type:
Ethernet IEEE 802.3 0...159 10...100 Mbit/s, RJ45 2 shielded twisted pairs
Ambient Air Temperature For Operation:
-20-60°C
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Connections - Terminals:
control circuit connector 1 0.25-2.5 mm² AWG 24...AWG 14)flexible with cable end || control circuit connector 1 0.2-2.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 1 0.25-2.5 mm² AWG 24...AWG 14)flexible without cab
Electromagnetic Compatibility:
electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || control circuit: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 || communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 || relay ou
Device Application:
equipment monitoring and control
Communication Port Protocol:
Modbus TCP/EtherNet/IP
Rohs Exemption Information:
Yes
Measurement Current:
5-100 A
Product Name:
TeSys T
Environmental Disclosure:
ENVPEP060308EN_V2
Current State 1 Guaranteed:
logic input < 15 V 2...15 mA 15 ms
[Us] Rated Supply Voltage:
24 V DC
Ip Degree Of Protection:
IP20
Operating Altitude:
<= 6561.68 ft (2000 m) without derating
Net Weight:
0.53 kg
[Ui] Rated Insulation Voltage:
690 V EN/IEC 60947-1 || 690 V CSA C22.2 No 14 || 690 V UL 508
Supply Voltage Limits:
20.4-26.24 V DC
[Uimp] Rated Impulse Withstand Voltage:
6 kV current or voltage measurement circuit EN/IEC 60947-4-1 || 0.8 kV communication circuit EN/IEC 60947-4-1 || 0.8 kV supply, inputs and outputs EN/IEC 60947-4-1
Protection Type:
locked rotor || overload || thermal overload protection || earth-leakage protection || reverse polarity protection || overload (long time) || power factor variation || phase unbalance || load fluctuation || phase failure || thermal protection
Ambient Air Temperature For Storage:
-40-80°C
Measurement Accuracy:
5...15 % earth fault current internal measurement || 1 % voltage 100...830 V) || 3 % power factor || 5 % earth fault current external measurement || +/- 30 min/year internal clock || 0,02 Temperature || 5 % active and reactive power || 0,02 current
Permissible Power:
480 VA AC-15), Ie = 2 A, 500000 cycles output) || 30 W DC-13), Ie = 1.25 A, 500000 cycles output)
Maximum Operating Rate:
1800 cyc/h
Mercury Free:
Yes
Tightening Torque:
control circuit 0.5-0.6 N.m flat 3 mm
Overvoltage Category:
III
Current State 0 Guaranteed:
logic input < 5 V <= 15 mA 5 ms
Load Current:
5 A 250 V AC logic output || 5 A 30 V DC logic output
Metering Type:
average current Iavg || earth-fault current || temperature || phase current I1, I2, I3 RMS || imbalance current
Country of Origin:
China
Mechanical Robustness:
vibrations mounted on symmetrical rail1 Gn, 5...300 Hz EN/IEC 60068-2-6 || vibrations plate mounted4 Gn, 5...300 Hz EN/IEC 60068-2-6 || shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27
Maximum Operating Frequency:
2 Hz
Associated Fuse Rating:
4 A gG output || 0.5 A gG control circuit
Compatibility Code:
LTMR
Eu Rohs Directive:
Compliant with Exemptions
Weight:
0.53 kg
Network And Machine Diagnosis Type:
fault recording || trip context information || waiting time after overload tripping || trip history information || running hours counter/operating time || motor control command recording || starting current and time || phase fault and earth fault tri
Input Current:
7 mA
$1,025.00

Description

TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. TeSys T manages most critical processes while reducing downtime and increasing productivity. TeSys T is a flexible system that integrates seamlessly into your automation system through five major communication protocols. TeSys T predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range. This controller is the central component in the motor management system. The module manages the basic functions of the motor management system. It manages the measurement of 3 phase current via integral current transformers from 0.4 to 100 A or up to 810 A by external current transformers. It also measures ground current with internal or external ground sensors, motor temperature and the inputs and outputs for the various motor control modes, detected fault management and other functions. Ethernet/IP and Modbus/TCP protocol is used by this controller. Ethernet TCP/IP communication is used. This module has 6 discrete logic inputs, 3 relay logic outputs and a relay output for detected fault signaling overload relay. The current range of this controller is 5 to 100 amperes. 24 VDC is used to power this controller. Controller has the following certifications: UL, CSA NOM, ATEX, BV, EAC, RINA, LROS, DNV, ABS, GL, KERI, RMRoS, C-Tick and CCC.
View AllClose