Schneider Electric

Schneider Electric LTMR27CBD Motor controller, TeSys T, Motor Management, CANopen, 6 logic inputs, 3 relay logic outputs, 1.35 to 27A, 24VDC

(No reviews yet) Write a Review
SKU:
LTMR27CBD
MPN:
LTMR27CBD
Condition:
New
Depth:
122.5 mm
[Uimp] Rated Impulse Withstand Voltage:
6 kV current or voltage measurement circuit EN/IEC 60947-4-1 || 0.8 kV communication circuit EN/IEC 60947-4-1 || 0.8 kV supply, inputs and outputs EN/IEC 60947-4-1
Environmental Disclosure:
ENVPEP060308EN_V2
Current State 1 Guaranteed:
logic input < 15 V 2...15 mA 15 ms
Measurement Accuracy:
5...15 % earth fault current internal measurement || 1 % voltage 100...830 V) || 3 % power factor || 5 % earth fault current external measurement || +/- 30 min/year internal clock || 0,02 Temperature || 1 % current || 5 % active and reactive power
Associated Fuse Rating:
4 A gG output || 0.5 A gG control circuit
Circularity Profile:
ENVEOLI100411EN_V2
Range:
TeSys
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Net Weight:
0.53 kg
Current Consumption:
56...127 mA
Bus Type:
CANopen ISO 1198 1...127 10...1000 kbit/s, SUB-D 9 4 twisted shielded pairs cable || CANopen ISO 1198 1...127 10...1000 kbit/s, terminal block 4 twisted shielded pairs cable
Communication Port Protocol:
CANopen
[Us] Rated Supply Voltage:
24 V DC
Halogen Content Performance:
Halogen free plastic parts product
Measurement Current:
1.35-27 A
Device Short Name:
LTMR
Connection Pitch:
5.08 mm
Operating Altitude:
<= 6561.68 ft (2000 m) without derating
Current State 0 Guaranteed:
logic input < 5 V <= 15 mA 5 ms
Tightening Torque:
control circuit 0.5-0.6 N.m flat 3 mm
Contacts Type And Composition:
1 NO + 1 NC fault signal || 3 NO
Sustainable Offer Status:
Green Premium product
Product Or Component Type:
motor controller
Supply Voltage Limits:
20.4-26.24 V DC
Pollution Degree:
3
Overvoltage Category:
III
Network And Machine Diagnosis Type:
phase fault and earth fault trip counters || trip context information || waiting time after overload tripping || fault recording || remaining operating time before overload tripping || starting current and time || motor control command recording || e
Product Certifications:
CSA || DNV || RINA || KERI || NOM || BV || CCC || EAC || ATEX || ABS || LROS (Lloyds register of shipping) || C-tick || GL || UL || RMRoS
Short-Circuit Withstand:
100 kA conforming to EN/IEC 60947-4-1
Load Current:
5 A 250 V AC logic output || 5 A 30 V DC logic output
Product Name:
TeSys T
Logic Input Number:
6
Mechanical Robustness:
vibrations mounted on symmetrical rail1 Gn, 5...300 Hz EN/IEC 60068-2-6 || vibrations plate mounted4 Gn, 5...300 Hz EN/IEC 60068-2-6 || shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Device Application:
equipment monitoring and control
Ambient Air Temperature For Storage:
-40-80°C
Rohs Exemption Information:
Yes
Metering Type:
temperature || imbalance current || phase current I1, I2, I3 RMS || earth-fault current || average current Iavg
Input Current:
7 mA
Weight:
0.53 kg
Warranty:
18 months
Maximum Operating Frequency:
2 Hz
Ip Degree Of Protection:
IP20
Protective Treatment:
12 x 24 hour cycles EN/IEC 60068-2-30 || 48 h EN/IEC 60070-2-11 || TH EN/IEC 60068
Country of Origin:
France
Width:
91 mm
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Compatibility Code:
LTMR
Mercury Free:
Yes
$1,125.00