Schneider Electric LTMR27DFM Motor Management, TeSys T, motor controller, DeviceNet, 6 inputs, 3 relay outputs, 1.35 to 27A, 100 to 240 VAC
Schneider Electric
$750.00
TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. TeSys T manages most critical processes while reducing downtime and increasing productivity. TeSys T is a flexible system that integrates seamlessly into your automation system through five major communication protocols. TeSys T predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range. This controller is the central component in the motor management system. The module manages the basic functions of the motor management system. It manages the measurement of 3 phase current via integral current transformers from 0.4 to 100 A or up to 810 A by external current transformers. It also measures ground current with internal or external ground sensors, motor temperature and the inputs and outputs for the various motor control modes, detected fault management and other functions. DeviceNet protocol is used by this controller. This module has 6 discrete logic inputs, 3 relay logic outputs and a relay output for detected fault signaling overload relay. The current range of this controller is 1.35 to 27 amperes. 120 to 240 VAC is used to power this controller. Controller has the following certifications: UL, CSA NOM, ATEX, BV, EAC, RINA, LROS, DNV, ABS, GL, KERI, RMRoS, C-Tick and CCC.
- Web Services:
- web server
- Metering Type:
- imbalance current || temperature || earth-fault current || average current Iavg || phase current I1, I2, I3 RMS
- Connection Pitch:
- 5.08 mm
- Bus Type:
- DeviceNet ISO 1198 1...64 125...500 kbit/s, terminal block 4 twisted shielded pairs cable
- Fire Resistance:
- 650°C EN/IEC 60695-2-12 || 960°C UL 94
- Ambient Air Temperature For Operation:
- -20-60°C
- Product Or Component Type:
- motor controller
- Connections - Terminals:
- control circuit connector 1 0.25-2.5 mm² AWG 24...AWG 14)flexible with cable end || control circuit connector 1 0.2-2.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 1 0.25-2.5 mm² AWG 24...AWG 14)flexible without cab
- Height:
- 61 mm
- Tightening Torque:
- control circuit 0.5-0.6 N.m flat 3 mm
- Mercury Free:
- Yes
- Rohs Exemption Information:
- Yes
- Short-Circuit Withstand:
- 100 kA conforming to EN/IEC 60947-4-1
- Operating Altitude:
- <= 6561.68 ft (2000 m) without derating
- [Uimp] Rated Impulse Withstand Voltage:
- 4 kV supply, inputs and outputs EN/IEC 60947-4-1 || 6 kV current or voltage measurement circuit EN/IEC 60947-4-1 || 0.8 kV communication circuit EN/IEC 60947-4-1
- Permissible Power:
- 480 VA AC-15), Ie = 2 A, 500000 cycles output) || 30 W DC-13), Ie = 1.25 A, 500000 cycles output)
- Contacts Type And Composition:
- 1 NO + 1 NC fault signal || 3 NO
- Net Weight:
- 0.53 kg
- Product Name:
- TeSys T
- Network And Machine Diagnosis Type:
- trip history information || trip context information || running hours counter/operating time || remaining operating time before overload tripping || fault recording || waiting time after overload tripping || starting current and time || phase fault a
- Maximum Operating Rate:
- 1800 cyc/h
- Sustainable Offer Status:
- Green Premium product
- Measurement Current:
- 1.35-27 A
- Range:
- TeSys
- Protection Type:
- thermal overload protection || power factor variation || phase failure || overload (long time) || reverse polarity protection || earth-leakage protection || thermal protection || locked rotor || load fluctuation || overload || phase unbalance
- Communication Port Protocol:
- DeviceNet
- Load Current:
- 5 A 250 V AC logic output || 5 A 30 V DC logic output
- Environmental Disclosure:
- ENVPEP060308EN_V2
- Pvc Free:
- Yes
- Protective Treatment:
- 12 x 24 hour cycles EN/IEC 60068-2-30 || 48 h EN/IEC 60070-2-11 || TH EN/IEC 60068
- Standards:
- EN 60947-4-1 || IACS E10 || UL 508 || CSA C22.2 No 14 || IEC 60947-4-1
- Maximum Operating Frequency:
- 2 Hz
- Device Short Name:
- LTMR
- Depth:
- 122.5 mm
- Weight:
- 0.53 kg
- Input Current:
- 3.1 mA 100 V || 7.5 mA 240 V
- [Us] Rated Supply Voltage:
- 100...240 V AC 50/60 Hz
- Eu Rohs Directive:
- Compliant with Exemptions
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Associated Fuse Rating:
- 4 A gG output || 0.5 A gG control circuit
- Supply Voltage Limits:
- 93.5-264 V AC
- Warranty:
- 18 months
- Halogen Content Performance:
- Halogen free plastic parts product
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Ip Degree Of Protection:
- IP20
- Circularity Profile:
- ENVEOLI100411EN_V2
- Measurement Accuracy:
- 5...15 % earth fault current internal measurement || 1 % voltage 100...830 V) || 3 % power factor || 5 % earth fault current external measurement || +/- 30 min/year internal clock || 0,02 Temperature || 1 % current || 5 % active and reactive power
- Overvoltage Category:
- III