Schneider Electric LTMR27EBD Motor Management, TeSys T, motor controller, Ethernet/IP, Modbus/TCP, 6inputs, 3logic outputs, 1.35A to 27A, 24VDC
Schneider Electric
$905.00
TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. TeSys T manages most critical processes while reducing downtime and increasing productivity. TeSys T is a flexible system that integrates seamlessly into your automation system through five major communication protocols. TeSys T predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range. This controller is the central component in the motor management system. The module manages the basic functions of the motor management system. It manages the measurement of 3 phase current via integral current transformers from 0.4 to 100 A or up to 810 A by external current transformers. It also measures ground current with internal or external ground sensors, motor temperature and the inputs and outputs for the various motor control modes, detected fault management and other functions. Ethernet/IP and Modbus/TCP protocol is used by this controller. Ethernet TCP/IP communication is used. This module has 6 discrete logic inputs, 3 relay logic outputs and a relay output for detected fault signaling overload relay. The current range of this controller is 1.35 to 27 amperes. 24 VDC is used to power this controller. Controller has the following certifications: UL, CSA NOM, ATEX, BV, EAC, RINA, LROS, DNV, ABS, GL, KERI, RMRoS, C-Tick and CCC.
- Overvoltage Category:
- III
- Country of Origin:
- China
- Protective Treatment:
- 12 x 24 hour cycles EN/IEC 60068-2-30 || 48 h EN/IEC 60070-2-11 || TH EN/IEC 60068
- Sustainable Offer Status:
- Green Premium product
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Ambient Air Temperature For Storage:
- -40-80°C
- Ip Degree Of Protection:
- IP20
- Operating Altitude:
- <= 6561.68 ft (2000 m) without derating
- Bus Type:
- Ethernet IEEE 802.3 0...159 10...100 Mbit/s, RJ45 2 shielded twisted pairs
- Protection Type:
- earth-leakage protection || phase failure || thermal protection || overload || overload (long time) || reverse polarity protection || power factor variation || phase unbalance || thermal overload protection || load fluctuation || locked rotor
- [Us] Rated Supply Voltage:
- 24 V DC
- Mercury Free:
- Yes
- Connection Pitch:
- 5.08 mm
- Network And Machine Diagnosis Type:
- remaining operating time before overload tripping || running hours counter/operating time || waiting time after overload tripping || phase fault and earth fault trip counters || fault recording || trip context information || trip history information
- Communication Port Protocol:
- Modbus TCP/EtherNet/IP
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || IACS E10 || IEC 60947-4-1 || UL 508
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Fire Resistance:
- 650°C EN/IEC 60695-2-12 || 960°C UL 94
- Input Current:
- 7 mA
- Current State 0 Guaranteed:
- logic input < 5 V <= 15 mA 5 ms
- [Ui] Rated Insulation Voltage:
- 690 V EN/IEC 60947-1 || 690 V CSA C22.2 No 14 || 690 V UL 508
- Rohs Exemption Information:
- Yes
- Circularity Profile:
- ENVEOLI100411EN_V2
- Logic Input Number:
- 6
- Electromagnetic Compatibility:
- electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || control circuit: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 || communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 || relay ou
- Supply Voltage Limits:
- 20.4-26.24 V DC
- Product Or Component Type:
- motor controller
- Measurement Current:
- 1.35-27 A
- Short-Circuit Withstand:
- 100 kA conforming to EN/IEC 60947-4-1
- Current State 1 Guaranteed:
- logic input < 15 V 2...15 mA 15 ms
- Web Services:
- web server
- Warranty:
- 18 months
- Compatibility Code:
- LTMR
- Range:
- TeSys
- Measurement Accuracy:
- 5...15 % earth fault current internal measurement || 1 % voltage 100...830 V) || 3 % power factor || 5 % earth fault current external measurement || +/- 30 min/year internal clock || 0,02 Temperature || 1 % current || 5 % active and reactive power
- Net Weight:
- 0.53 kg
- Permissible Power:
- 480 VA AC-15), Ie = 2 A, 500000 cycles output) || 30 W DC-13), Ie = 1.25 A, 500000 cycles output)
- Maximum Operating Rate:
- 1800 cyc/h
- Ambient Air Temperature For Operation:
- -20-60°C
- Product Certifications:
- CCC || BV || KERI || C-tick || GL || ATEX || RINA || CSA || EAC || UL || NOM || DNV || LROS (Lloyds register of shipping) || ABS || RMRoS
- Environmental Disclosure:
- ENVPEP060308EN_V2
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Contacts Type And Composition:
- 1 NO + 1 NC fault signal || 3 NO
- Maximum Operating Frequency:
- 2 Hz
- Halogen Content Performance:
- Halogen free plastic parts product
- Metering Type:
- phase current I1, I2, I3 RMS || average current Iavg || imbalance current || earth-fault current || temperature