TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. It manages most critical processes while reducing downtime and increasing productivity as well as predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range. This motor management system is also a flexible system that supports six communication protocols which are Modbusâ„¢, CANopen, DeviceNetâ„¢, Profibusâ„¢, Ethernet/IP, and Modbus/TCP. TeSys T motor management system consist of several components which include the LTMR controller, the expansion module, HMI and software along with several accessories. The LTMR controller is the main component of the system that manages the basic functions. This includes the measurement of the ground current, motor temperature, three phase current of the motor, the controller also includes logic inputs and outputs which is used in fault management. The expansion module is directly connected to the controller and provides additional inputs as well as measure the voltage between the phases which allow the controller the monitor additional functions. TeSys T is highly reliable and has a very long product life thanks to a state-of-the-art component selection, to the all in one design and to the advanced electronic protection. TeSys T can be integrated in many different types of harsh environment such as dusty atmospheres, marine applications, high vibration applications and corrosive atmospheres and is used in Metal/Mining/Mineral, Oil & Gas, Water Wastewater. This is a TeSys T LTMR controller that measure current range of 1.35-27A with a supply voltage of 100-240 Vac and uses CANopen as the communication protocol. This controller measures temperature, phase current, imbalance current, average current and earth-fault current. The dimensions of this device are 61 mm (H) X 91 mm (W) X 122.5 mm (D) and it weighs 0.53 kg.
- Range:
- TeSys
- Protective Treatment:
- 12 x 24 hour cycles EN/IEC 60068-2-30 || 48 h EN/IEC 60070-2-11 || TH EN/IEC 60068
- Device Application:
- equipment monitoring and control
- Electromagnetic Compatibility:
- electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 || relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5 ||
- [Uimp] Rated Impulse Withstand Voltage:
- 4 kV supply, inputs and outputs EN/IEC 60947-4-1 || 6 kV current or voltage measurement circuit EN/IEC 60947-4-1 || 0.8 kV communication circuit EN/IEC 60947-4-1
- Current State 0 Guaranteed:
- logic input 0...40 V <= 15 mA 25 ms
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Compatibility Code:
- LTMR
- Circularity Profile:
- ENVEOLI100411EN_V2
- Weight:
- 0.53 kg
- Product Name:
- TeSys T
- Mechanical Robustness:
- vibrations mounted on symmetrical rail1 Gn, 5...300 Hz EN/IEC 60068-2-6 || vibrations plate mounted4 Gn, 5...300 Hz EN/IEC 60068-2-6 || shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27
- Metering Type:
- temperature || phase current I1, I2, I3 RMS || average current Iavg || earth-fault current || imbalance current
- Associated Fuse Rating:
- 4 A gG output || 0.5 A gG control circuit
- Product Certifications:
- RMRoS || LROS (Lloyds register of shipping) || RINA || ABS || CCC || EAC || UL || GL || NOM || DNV || KERI || ATEX || BV || CSA || C-tick
- Eu Rohs Directive:
- Compliant with Exemptions
- Communication Port Protocol:
- Modbus
- Supply Voltage Limits:
- 93.5-264 V AC
- Tightening Torque:
- control circuit 0.5-0.6 N.m flat 3 mm
- Load Current:
- 5 A 250 V AC logic output || 5 A 30 V DC logic output
- Pollution Degree:
- 3
- Country of Origin:
- United States
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Rohs Exemption Information:
- Yes
- [Us] Rated Supply Voltage:
- 100...240 V AC 50/60 Hz
- Height:
- 61 mm
- Net Weight:
- 0.53 kg
- Overvoltage Category:
- III
- Network And Machine Diagnosis Type:
- fault recording || starting current and time || remaining operating time before overload tripping || waiting time after overload tripping || motor control command recording || event recording || trip history information || running hours counter/opera
- Measurement Accuracy:
- 5...15 % earth fault current internal measurement || 1 % voltage 100...830 V) || 3 % power factor || 5 % earth fault current external measurement || +/- 30 min/year internal clock || 0,02 Temperature || 1 % current || 5 % active and reactive power
- Contacts Type And Composition:
- 1 NO + 1 NC fault signal || 3 NO
- Device Short Name:
- LTMR
- Mercury Free:
- Yes
- Depth:
- 122.5 mm
- Operating Altitude:
- <= 6561.68 ft (2000 m) without derating
- Web Services:
- web server
- Permissible Power:
- 480 VA AC-15), Ie = 2 A, 500000 cycles output) || 30 W DC-13), Ie = 1.25 A, 500000 cycles output)
- Protection Type:
- reverse polarity protection || overload (long time) || earth-leakage protection || phase unbalance || overload || load fluctuation || phase failure || power factor variation || thermal protection || locked rotor || thermal overload protection
- Maximum Operating Rate:
- 1800 cyc/h
- Fire Resistance:
- 650°C EN/IEC 60695-2-12 || 960°C UL 94
- [Ui] Rated Insulation Voltage:
- 690 V EN/IEC 60947-1 || 690 V CSA C22.2 No 14 || 690 V UL 508
- Width:
- 91 mm
- Input Current:
- 3.1 mA 100 V || 7.5 mA 240 V
- Product Or Component Type:
- motor controller
- Connection Pitch:
- 5.08 mm
- Measurement Current:
- 1.35-27 A
- Connections - Terminals:
- control circuit connector 1 0.25-2.5 mm² AWG 24...AWG 14)flexible with cable end || control circuit connector 1 0.2-2.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 1 0.25-2.5 mm² AWG 24...AWG 14)flexible without cab
- Pvc Free:
- Yes
- Ip Degree Of Protection: