Schneider Electric LX1G3TEHEN Control module, LX1G, TeSys Giga, standard contactor, 48-130VAC/DC, for LC1G630-800, 3 pole
Schneider Electric
$235.00
It is a 48-130V AC/DC control module for 3 poles TeSys Giga 630-800 contactor (advanced version). Coil designed for less energy consumption and wider voltage band-width, connection by spring terminal. It allows contactor operation with high AC-3 operating rates until 600 cycles/hour and environments until 60°C. Control module has connectors for connecting the coil control A1, A2 circuit, pole status and diagnostic signaling circuits. Local Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It is accessible from the front and maintained with very low down times. Unique QR code provides quick access to complete product data.
- Depth:
- 211 mm
- [Uc] Control Circuit Voltage:
- 48...130 V AC/DC 50/60 Hz
- Electromagnetic Compatibility:
- EMC immunity conforming to IEC 60947-4-1 || emission tests criteria A conforming to IEC 60947-4-1 || immunity to radiated radio-electrical interference - test level: 20 V/m conforming to EN/IEC 61000-4-3 || voltage dips and interruptions immunity tes
- Quantity Per Set:
- 1
- Control Circuit Voltage Limits:
- operational 0.8...1.1 Uc 60°C) || drop-out 0...0.45 Uc 60°C)
- Weight:
- 2185 g
- Product Compatibility:
- LC1G630...800
- Ambient Air Temperature For Operation:
- -25-60°C
- Pvc Free:
- Yes
- Mercury Free:
- Yes
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For m
- Eu Rohs Directive:
- Compliant with Exemptions
- Pollution Degree:
- 3 IEC 60947-1
- Ambient Air Temperature For Storage:
- -60-80°C
- Ip Degree Of Protection:
- IP20 IEC 60529
- Halogen Content Performance:
- Halogen free plastic parts product
- Maximum Operating Rate:
- 600 cyc/mn 60°C
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Environmental Disclosure:
- ENVPEP2105013
- Permissible Ambient Air Temperature Around The Device:
- -40-70°C at Uc
- Rohs Exemption Information:
- Yes
- Poles Description:
- 3P
- Standards:
- EN/IEC 60947-4-1 || UL 60947-4-1A || CSA C22.2 No 60947-4-1
- China Rohs Regulation:
- X
- Circularity Profile:
- ENVEOLI2105013
- Operating Altitude:
- 9842.52 ft (3000 m) without derating || 5000 m with derating factor
- Country of Origin:
- China
- Range Compatibility:
- TeSys G LX1G contactor coil
- Range:
- TeSys
- Net Weight:
- 2185 g
- Operating Time:
- 20...35 ms opening || 40...55 ms closing
- Product Or Component Type:
- contactor coil
- Connections - Terminals:
- control circuit push-in termination 1 0.2-2.5 mm² solid stranded without cable end sleeve AWG 26...AWG 12 || control circuit push-in termination 1 0.25-2.5 mm² flexible with cable end sleeve AWG 24...AWG 14 || control circuit push-in termination 2
- Device Short Name:
- LX1G
- Coil Technology:
- built-in bidirectional peak limiting
- Mechanical Durability:
- 5 Mcycles
- Sustainable Offer Status:
- Green Premium product