- [Uc] Control Circuit Voltage:
- 220...230 V AC 40...400 Hz || 220...230 V DC
- Toxic Heavy Metal Free:
- Yes
- Rohs Exemption Information:
- Yes
- Mechanical Durability:
- 10 Mcycles
- Inrush Power In Va:
- 550-550 VA 40...400 Hz (at 20°C)
- Net Weight:
- 1.08 kg
- Range Compatibility:
- TeSys TeSys F LC1F contactor || TeSys TeSys F DR5TE rectifier
- Mercury Free:
- Yes
- Eu Rohs Directive:
- Pro-active compliance (Product out of EU RoHS legal scope)
- Operating Time:
- 60 ms opening || 50 ms closing
- Maximum Operating Rate:
- 3600 cyc/h 70°C
- Range:
- TeSys
- Device Short Name:
- LX9FK
- Reach Free Of Svhc:
- Yes
- Warranty:
- 18 months
- Control Circuit Type:
- AC 40...400 Hz low consumption || DC low consumption
- Heat Dissipation:
- 15-18.3 W
- Weight:
- 1.08 kg
- Environmental Disclosure:
- ENVPEP1505009EN
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Ambient Air Temperature For Operation:
- -5-55°C
- Hold-In Power Consumption In Va:
- 31-31 VA 40...400 Hz (at 20°C)
- Country of Origin:
- Czechia
- Sustainable Offer Status:
- Green Premium product
- Product Compatibility:
- LC1F500 || DR5TE
- Product Or Component Type:
- specific contactor coil
- Inductance Of Closed Circuit:
- 4 H
- Control Circuit Voltage Limits:
- operational 0.85...1.1 Uc 55°C) || drop-out 0.3...0.5 Uc 55°C)
- Coil Technology:
- without built-in suppressor module
- Average Resistance:
- 89.9 Ohm inrush 20°C || 770 Ohm holding 20°C
- China Rohs Regulation:
- X
- Circularity Profile:
- ENVEOLI1505009EN