Schneider Electric

Schneider Electric METSEEM3561 PowerLogic EM3500 DIN rail meter - BACnet without logging - current transformer

(No reviews yet) Write a Review
SKU:
METSEEM3561
MPN:
METSEEM3561
Condition:
New
Technology Type:
electronic
Relative Humidity:
0-95 %
Communication Port Protocol:
BACnet MS/TP 9600 bauds...115200 bauds (automatic detection) - 2-wire
Mercury Free:
Yes
Eu Rohs Directive:
Compliant with Exemptions
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Data Recording:
energy consumption logs
[Ue] Rated Operational Voltage:
90...347 V AC 50/60 Hz between phase and neutral UL || 156...600 V AC 50/60 Hz between phases UL || 90...300 V AC 50/60 Hz between phase and neutral CE || 125...300 V DC
Product Or Component Type:
energy meter
Type Of Measurement:
active and reactive power total || active and reactive power per phase || apparent power total || apparent power per phase || power factor total || power factor per phase || peak demand power || current || voltage || frequency
Local Signaling:
Red LED threshold reached || Green flashing LED output signal
Analogue Input Type:
split core current transducer 0.333 V or 1 V
Tamperproof Of Settings:
protected by access code
Ambient Air Temperature For Operation:
-30-70°C
Product Certifications:
CE conforming to IEC 61010 || cULus conforming to UL 508
Product Name:
PowerLogic EM3500
Display Type:
Backlit LCD
Ambient Air Temperature For Storage:
-40-85°C
Measurement Accuracy:
power +/- 0.2 % || energy +/- 0.2 %
Rohs Exemption Information:
Yes
Measurement Current:
5-32000 A
Device Application:
sub billing || partial meter
Country of Origin:
United States
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Standards:
UL 508 || CSA C22.2 No 14-05 || IEC 61010-1
Device Short Name:
EM3561
China Rohs Regulation:
X
Communication Port Support:
screw terminal block RS485
Power Consumption In Va:
5-5 VA 347 V AC between phase and neutral) || 5-5 VA 600 V AC between phases)
Metering Type:
peak demand power PM, QM, SM || current I1, I2, I3, Iavg || demand power P, Q, S || voltage U21, U32, U13, V1, V2, V3
Depth:
59 mm
Poles Description:
3P + N
Number Of Inputs:
2 pulse
Display Digits:
5
Range:
PowerLogic
Mounting Mode:
clip-on || by screws
Function Available:
external synchronisation to communication || fixed or rolling block
Color:
dark grey
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Ride-Through Time:
100 ms 120 V AC
Mounting Support:
DIN rail
Power Consumption In W:
3 W 300-300 V
Information Displayed:
status and alert || communication with system || input/output status || error || Tx activity || Rx activity || instant power per usage
Communication Service:
total cumulated active energy || total cumulated energy
9 Mm Pitches:
12
Accuracy Class:
class 0.2S power IEC 62053-22 || class 0.2S energy IEC 62053-22 || class 0.2S power ANSI C12.20 || class 0.2S energy ANSI C12.20
$1,249.63

Description

The EM3500 series offer a three-phases DIN rail-mounted energy meters fitted for accurate cost allocation and sub-metering. EM35xx models are designed for use with Low Votage Current Transducers 1/3Volt or 1Volt output. Current input from 5A to 32000A, according to the LVCT configuration in the HMI, ANSI C12.20 0.2% accuracy, IEC 62053-22 class 0.2S. Native BACnet is provided to suit a wide variety of applications. Additional 2 pulse inputs provide an easy way to incorporate simple WAGES sensors using a BACnet system. Suitable for a 230V AC network, with a supply voltage range of 90V AC to 300V AC at 50Hz or 60Hz. Compliant with UL508, CSA 22.2 number 14-05 and EN 61010-1. Product dimensions are as follows: width 107 mm, depth 59 mm, height 91 mm.
View AllClose