Schneider Electric

Schneider Electric METSEPM2130 EasyLogic PM2130, Power & Energy meter, up to the 31st harmonic, LED display, RS485, class 0.5S

(No reviews yet) Write a Review
SKU:
METSEPM2130
MPN:
METSEPM2130
Condition:
New
Mounting Support:
framework
Mounting Mode:
clip-on
Measurement Current:
5-6000 mA
Metering Type:
peak demand currents || active power P, P1, P2, P3 || demand power P, Q, S || reactive power Q, Q1, Q2, Q3 || apparent power S, S1, S2, S3 || active, reactive, apparent energy (signed, four quadrant) || voltage U, U21, U32, U13, V, V1, V2, V3 || curr
Electromagnetic Compatibility:
electrostatic discharge conforming to IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3 || electrical fast transient/burst immunity test conforming to IEC 61000-4-4 || surge immunity test confor
Provided Equipment:
1 x Installation guide
Mercury Free:
Yes
Material:
polycarbonate
Analogue Input Type:
current (impedance <= 0.3 mOhm) || voltage (impedance > 5 MOhm)
Communication Port Support:
screw terminal block RS485
Tamperproof Of Settings:
protected by access code
Network Frequency:
50 Hz || 60 Hz
Refresh Time:
configurable from 1 to 60 min
Display Type:
7 segments LED
Display Colour:
red
Operating Altitude:
<= 6561.68 ft (2000 m)
Number Of Inputs:
0
Communication Port Protocol:
Modbus RTU 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps even/odd or none - 2 wires 2500 V
Number Of Outputs:
0
Measurement Accuracy:
apparent power +/- 0.5 % || active energy +/- 0.5 % || reactive energy +/- 1 % || active power +/- 0.5 % || voltage +/- 0.5 % || power factor +/- 0.01 || current +/- 0.5 % || frequency +/- 0.05 %
Flame Retardance:
V-0 conforming to UL 94
[Us] Rated Supply Voltage:
80...277 V AC 45...65 Hz +/- 10 % || 100...277 V DC +/- 10 %
Pollution Degree:
2
Display Digits:
12 - 14.2 mm
Depth:
total : 76.09 mm || embedded : 61.64 mm
Measurement Voltage:
35-480 V AC 50/60 Hz between phases || 20-277 V AC 50/60 Hz between phase and neutral || 480-999000 V AC 50/60 Hz with external VT
Maximum Power Consumption In W:
3.3 W power lines (AC)) || 3.3 W 277 V power lines (DC))
Range:
EasyLogic
Sampling Rate:
64 samples/cycle
Type Of Measurement:
apparent power min/max, total || active and reactive power min/max, total || current min/max, avg || voltage min/max, avg || frequency min/max, avg || total current harmonic distortion THD (I) per phase || total voltage harmonic distortion THD (U) pe
Cybersecurity:
enable/disable communication ports
Data Recording:
power logs || time stamping || energy consumption logs || min/max for 8 parameters
Product Or Component Type:
power meter
Frequency Measurement Range:
45-65 Hz
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Local Signaling:
Red LED output signal 1...9999000 pulse/ k_h (kWh, kVAh, kVARh) || Green LED module operation and integrated communication
Weight:
300 g
Accuracy Class:
class 1 reactive energy IEC 62053-24 || class 0.5S active energy IEC 62053-22 || class 5 harmonic distorsion (I THD & U THD)
China Rohs Regulation:
X
Product Certifications:
CE conforming to IEC 61010-1 || cULus conforming to UL 61010-1 || cULus conforming to CSA C22.2 No 61010-1 || RCM || EAC || C-tick
Sustainable Offer Status:
Green Premium product
Environmental Disclosure:
ENVPEP1510002
Relative Humidity:
5-95 % 50-50°C
Messages Display Capacity:
3 fields of 4 characters
Service Life:
7 year(s)
Ip Degree Of Protection:
IP54 front: conforming to IEC 60529 || IP30 body: conforming to IEC 60529
$866.55

Description

This device is a panel mount or flush mount power meter with a 96mm by 96mm bezel size having 3 rows of bright red 4 digits 14.2 mm height LED display. The meter measures active energy as per accuracy class Class 0.5S complying to IEC 62053-22 standard with sampling rate of 64 samples per cycle. Able to measures all three vectors of power and energy such as Active, Apparent & Reactive beside Voltages, Current, Frequency and Power Factor. Plus the total Harmonic Distortion and Individual harmonics up to 31st Harmonic order. The meter will function in either 50Hz or 60Hz network frequency and accepts universal control power voltages ranging from 80 to 300 V Line to Neutral AC or DC voltages. Rated current for this meter is either 1A or 5A input. it supports up to 13 different types of wiring schemes under Single Phase, Two Phase or Three Phase configuration types. The range of measurement voltage between Phases is 35 to 480 V Line to Line AC at 45 to 65 Hz while it is 20 to 277 V between Line and Neutral. It is having RS485 communication port over Modbus RTU protocol. The meter can be upgraded with optional add on IO modules for WAGES monitoring. These module comes with either two channels each of digital inputs and outputs or analog inputs and outputs. This version can be configured for 23 different types of alarms stored in 40 registers. Product dimensions are as follows: width 3.78 in (96 mm), depth 2.16 in (54 mm), height 3.78 in (96 mm) and product weight 10.58 oz (300 g).
View AllClose