Schneider Electric

Schneider Electric METSEPM2220 EasyLogic PM2220, Power & Energy meter, up to the 15th harmonic, LCD display, RS485, class 1

(No reviews yet) Write a Review
SKU:
METSEPM2220
MPN:
METSEPM2220
Condition:
New
Net Weight:
300 g
Electromagnetic Compatibility:
electrostatic discharge conforming to IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3 || electrical fast transient/burst immunity test conforming to IEC 61000-4-4 || surge immunity test confor
Depth:
total : 76.09 mm || embedded : 61.64 mm
Information Displayed:
demand current past value) || demand current present value) || demand power past value) || demand power present value) || voltage || current || frequency || energy consumption || harmonic distortion || power factor || active power || apparent power |
Mercury Free:
Yes
Flame Retardance:
V-0 conforming to UL 94
Mounting Mode:
clip-on
Mounting Support:
framework
Communication Service:
remote monitoring
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Analogue Input Type:
current (impedance <= 0.3 mOhm) || voltage (impedance > 5 MOhm)
Measurement Accuracy:
apparent power +/- 1 % || active energy +/- 1 % || reactive energy +/- 1 % || active power +/- 1 % || voltage +/- 0.5 % || power factor +/- 0.01 || current +/- 0.5 % || frequency +/- 0.05 %
China Rohs Regulation:
X
Cybersecurity:
enable/disable communication ports
Type Of Measurement:
apparent power min/max, total || active and reactive power min/max, total || current min/max, avg || voltage min/max, avg || frequency min/max, avg || total current harmonic distortion THD (I) per phase || total voltage harmonic distortion THD (U) pe
Function Available:
real time clock
Measurement Voltage:
35-480 V AC 50/60 Hz between phases || 20-277 V AC 50/60 Hz between phase and neutral || 480-999000 V AC 50/60 Hz with external VT
Display Colour:
monochrome
Metering Type:
active, reactive, apparent energy (signed, four quadrant) || current I, I1, I2, I3 || peak demand currents || peak demand power PM, QM, SM || unbalance current || active power P, P1, P2, P3 || reactive power Q, Q1, Q2, Q3 || demand power P, Q, S || v
Compatibility Code:
PM2220
Control Type:
4 x button
Communication Port Protocol:
Modbus RTU 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps even/odd or none - 2 wires 2500 V
Power Quality Analysis:
total harmonic distortion || up to the 15th harmonic
Mounting Position:
vertical
User Language:
Spanish || French || English || Russian || Portuguese || German || Chinese
Eu Rohs Directive:
Compliant with Exemptions
Material:
polycarbonate
Display Resolution:
128 x 128 pixels
Service Life:
7 year(s)
Maximum Power Consumption In Va:
6 VA 277 V AC
Device Application:
power monitoring || sub billing
Ambient Air Temperature For Operation:
-10-60°C
Relative Humidity:
5-95 % 50-50°C
Tamperproof Of Settings:
protected by access code
Line Rated Current:
1 A || 5 A
Connections - Terminals:
current transformer screw connection bottom) 6 || voltage inputs screw connection top) 4
Width:
96 mm
Country of Origin:
India
Rohs Exemption Information:
Yes
Range:
EasyLogic
Measurement Current:
5-6000 mA
Measurement Category:
category III 480-480 V || category II 480-600 V
Environmental Disclosure:
ENVPEP1510004
Local Signaling:
Red LED output signal 1...9999000 pulse/ k_h (kWh, kVAh, kVARh) || Green LED module operation and integrated communication
Provided Equipment:
1 x Installation guide
Height:
96 mm
Circularity Profile:
ENVEOLI1510004
Communication Port Support:
screw terminal block RS485
Device Short Name:
PM2220
Number Of Outputs:
0
$633.31

Description

This device is a panel mount or flush mount power meter with a 96mm by 96mm bezel size having backlit LCD display of 128 by 128 pixels. The meter measures active energy as per accuracy class Class 1.0 complying to IEC 62053-21 standard with sampling rate of 64 samples per cycle. Able to measures all three vectors of power and energy such as Active, Apparent & Reactive beside Voltages, Current, Frequency and Power Factor. Plus the total Harmonic Distortion and Individual harmonics up to 15th Harmonic order. The meter will function in either 50Hz or 60Hz network frequency and accepts universal control power voltages ranging from 44 to 300 V Line to Neutral AC or DC voltages. Rated current for this meter is either 1A or 5A input. it supports up to 13 different types of wiring schemes under Single Phase, Two Phase or Three Phase configuration types. The range of measurement voltage between Phases is 35 to 480 V Line to Line AC at 45 to 65 Hz while it is 20 to 277 V between Line and Neutral. It is having RS485 communication port over Modbus RTU protocol. Product dimensions are as follows: width 3.78 in (96 mm), depth 2.16 in (54 mm), height 3.78 in (96 mm) and product weight 10.58 oz (300 g).
View AllClose