Schneider Electric

Schneider Electric METSEPM3255 PM3255 power meter - 2 digital I - 2 digital O - RS485

(No reviews yet) Write a Review
SKU:
METSEPM3255
MPN:
METSEPM3255
Condition:
New
Overvoltage Category:
III
Power Quality Analysis:
up to the 15th harmonic
Product Or Component Type:
power meter
Communication Port Support:
RS485
Type Of Measurement:
active and reactive power || apparent power || current || voltage || energy || power factor || frequency || total current harmonic distortion THD (I) || total voltage harmonic distortion THD (U)
Line Rated Current:
5 A || 1 A
Operating Altitude:
< 9842.52 ft (3000 m)
Analogue Input Type:
current 0...5 A || current 0...1 A
Ambient Air Temperature For Storage:
-40-85°C
Communication Port Protocol:
Modbus 9.6...38.4 kbauds
Device Short Name:
PM3255
[Us] Rated Supply Voltage:
100...277 V AC 45...65 Hz || 173...480 V AC 45...65 Hz || 100...300 V DC
Circularity Profile:
ENVEOLI111258EN
Country of Origin:
United States
Eu Rohs Directive:
Compliant with Exemptions
Product Certifications:
CE IEC 61010-1 safety) || CE EN 61557-12 power monitor) || CE EN/IEC 61326-1 EMC) || UKCA BS EN 61010-1 safety) || UKCA BS EN 61557-12 power monitor) || UKCA BS EN 61326-1 EMC) || cULus EN 61010-1 safety) || cULus UL 61010-1 safety) || EAC sub-meter)
Pollution Degree:
2
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Measurement Accuracy:
current 0.3 % 0.5...6 A || current 0.5 % 0.1...1.2 A || voltage 0.3 % 50...330 V || voltage 0.3 % 80...570 V
Mounting Support:
DIN rail
Product Name:
PowerLogic PM3000
Sampling Rate:
32 samples/cycle
Device Application:
multi-tariff || power monitoring || sub billing
Measurement Current:
0.02-1.2 A || 0.05-6 A
Relative Humidity:
5-95 % 50-50°C
Display Resolution:
128 x 96 pixels
Net Weight:
0.26 kg
China Rohs Regulation:
X
Display Type:
Backlit LCD
Data Recording:
energy consumption logs || 15 alarms || power logs || time stamping || min/max of instantaneous values
Electromagnetic Compatibility:
electrostatic discharge level 4 conforming to IEC 61000-4-2 || susceptibility to electromagnetic fields level 3 conforming to IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 || surge immunity test le
Ambient Air Temperature For Operation:
-25-70°C
Power Consumption In Va:
5 VA
Rohs Exemption Information:
Yes
Poles Description:
3P || 3P + N || 1P + N
Warranty:
18 months
Memory Capacity:
512 KB
Accuracy Class:
class 0.5S active energy IEC 62053-22 || class 1 active energy IEC 62053-21 || class 2 reactive energy IEC 62053-23 || class C active energy EN 50470-3
Network Frequency:
60 Hz || 50 Hz
Mercury Free:
Yes
Number Of Inputs:
2 digital 0...4 mA 11...40 V DC
Depth:
70 mm
Information Displayed:
tariff 4)
Measurement Voltage:
50-330 V AC 45...65 Hz direct || 50-330 V AC 45...65 Hz phase to neutral || 80-570 V AC 45...65 Hz direct || 80-570 V AC 45...65 Hz phase to phase || 570-999000 V AC 45...65 Hz with external VT
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
$1,088.99

Description

PM3255 DIN mount energy meter with a 128 by 96 pixel backlit, LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 32 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor, Apparent Power, Total Harmonic Distortion and up to 15th Harmonic. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 277VAC, 173 to 480VAC and 100 to 300VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase, Single Phase and Neutral or Three Phase configurations. Direct measurement range is 50 to 570VAC, with an external VT 570 to 999000VAC. The range of measurement voltage between Phases is 80 to 570VAC at 45 to 65 Hz. Measurement range between Phase and Neutral is 50 to 330VAC at 45 to 65 Hz. Communication protocol is Modbus RTU and ASCII 2 wires with RS485 port support. Support for two digital input and two digital outputs. The meter offers 512kB of memory for event recording with up to 15 alarms with power and energy consumption logs. Product dimensions are as follows: width 3.54 in (90 mm), depth 2.76in (70 mm), height 3.74 in (95 mm) and product weight 9.17 oz (260 g).
View AllClose